Cleaning, Maintenance; Fault Rectification; Dismantling; Environmentally Responsible Disposal - Maico HDR 10 Mounting And Operating Instructions

Diagonal fans for duct installation
Hide thumbs Also See for HDR 10:
Table of Contents

Advertisement

Available languages

Available languages

UK │ 13. Cleaning, maintenance

13. Cleaning, maintenance

Cleaning: Before cleaning, switch off mains
fuse, secure against being accidentally
switched back on and position a warning
sign.
If required, the unit is cleaned with a dry
cloth. The operator should determine the
cleaning intervals – frequency depends on
ambient conditions and anticipated
impairments.
For cleaning the inside, open both brackets
[4], remove the fan unit and clean it with a dry
cloth.
Maintenance: HDR units are maintenance-
free. Despite this, check the unit from time to
time for bearing noise, damage and dispro-
portionate vibration.
If necessary, clean the unit of dirt/foreign
particles as described above. Never use
water or a high-pressure cleaner on the
interior.

14. Fault rectification

Fault finding and repairs only permis-
sible when carried out by trained
specialists.
Fault
Cause, measure
Fan does
No mains voltage.
not switch on.
Check whether the mains
fuse has failed. Switch on if
necessary.
Impeller not
Motor too hot, thermal
turning.
switch has triggered.
Leave the unit switched off
until the motor cools down.
Cool-down time can be
up to 30 minutes. Only
then, switch the unit back
on.
Impeller blocked.
Impeller not
Check impeller and clean if
turning.
necessary.
10
Deposits on the
Install air filter in duct
impeller and in
system.
the housing
Under no circumstances
caused by dust
should the inside of the unit
in the air.
be cleaned with water or a
high-pressure cleaner.
If the fault persists, disconnect unit
from the power supply, fit a sign
prohibiting it from being switched
back on and have cause of error
investigated by a trained electrician.
If faults reoccur, send the unit to our
factory for repairs.

15. Dismantling

Dismantling may only be undertaken
by a trained electrician.
16. Environmentally responsible
disposal
The unit and the packaging contain parts that
can be recycled, and should not end up in the
domestic waste.
Dispose of the packaging material in an
environmentally-friendly way, in compliance
with the regulations valid in the country where
you are.
At the end of its service life, dispose of the
unit in an environmentally-friendly way, in
compliance with the regulations valid in the
country where you are.