Code Description
R03 Activation delay for digital input 1
R04 Digital input 2 function
R05 Digital input 2 polarity
R06 Activation delay for digital input 2
R07 Digital input 3 function
R08 Digital input 3 polarity
R09 Activation delay for digital input 3
S01 Alarm contact activation in a warning, alarm, lockout
S02 Alarm relay deactivation
S03 Buzzer enabled
S04 Relay output 1 configuration
S05 Relay output 2 configuration
S06 Relay output 3 configuration
S07 Relay output 4 configuration
S08 Relay output 5 configuration
S09 Triac output 1 configuration
C6.1.6/0613-0915/E
Range
0 to 255 min
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
oP (0) - CL (1)
0 to 255 min
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
oP (0-OP) - CL (1-CL)
0 to 255 min
Warning(0-ARN) - Alarm(1-ALM) - Lockout(2-LOC)
No (0-NO) - Yes (1-YES)
No (0-NO) - Yes (1-YES)
Not used (0-NU)
DGS compressor (1-DGS)
On-Off compressor (2-CPR)
Condenser fan 1 (3-CF1)
Condenser fan 2 (4-CF2)
Evaporator fan (5-EPF)
Defrost (6-DEF)
Liquid line solenoid (7-LLS)
Crankcase heater (8-HTR)
Alarm (9-ALM)
Light (10-LIG)
Not used (0-NU)
Digital solenoid (1-DGT)
Wave Form chopper for fan speed (2-PCF)
PWM fan speed (3-PEF)
0-10V (4-UEF)
Factory Setting
ZXDE ZXME ZXLE
0
L2
High pressure input
N.V.
oP
N.V.
0
N.V.
Not used
L2
CL
L2
0
L2
Alarm
L2
YES
L2
NO
L2
Crankcase heater
N.V.
Not used
L2
DGS compressor
N.V.
Not used
L2
Alarm
L2
Digital solenoid
L2
L2
L2
N.V.
N.V.
N.V.
N.V.
N.V.
N.V.
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
N.V.
N.V.
L2
L2
N.V.
N.V.
L2
L2
L2
L2
L2
L2
53