RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA150S4D (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 72.0
21.1
3.62
63_F
4000 1890 76.0
22.3
3.63
(17_C)
4800 2265 78.9
23.1
3.65
3200 1510 76.4
22.4
3.63
67_F
4000 1890 80.5
23.6
3.65
(19_C)
4800 2265 83.5
24.5
3.66
3200 1510 80.6
23.6
3.65
71_F
4000 1890 85.1
24.9
3.67
(22_C)
4800 2265 88.2
25.8
3.68
COOLING CAPACITY − TSA150S4D (SECOND STAGE) with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 133.5 39.1
8.99
63_F
4000 1890 140.7 41.2
9.01
(17_C)
4800 2265 146.1 42.8
9.02
3200 1510 142.0 41.6
9.01
67_F
4000 1890 149.3 43.8
9.02
(19_C)
4800 2265 155.3 45.5
9.04
3200 1510 150.5 44.1
9.03
71_F
4000 1890 158.2 46.4
9.05
(22_C)
4800 2265 163.8 48.0
9.06
COOLING CAPACITY − TSA150S4D (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
4000 1890 75.2
22.0
3.63
63_F
5000 2360 78.9
23.1
3.64
(17_C)
6000 2830 82.2
24.1
3.65
4000 1890 80.2
23.5
3.65
67_F
5000 2360 83.9
24.6
3.66
(19_C)
6000 2830 86.7
25.4
3.67
4000 1890 85.1
24.9
3.67
71_F
5000 2360 89.0
26.1
3.68
(22_C)
6000 2830 91.9
26.9
3.69
COOLING CAPACITY − TSA150S4D (SECOND STAGE) with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
4000 1890 139.9 41.0
9.00
63_F
5000 2360 146.8 43.0
9.03
(17_C)
6000 2830 152.8 44.8
9.03
4000 1890 149.1 43.7
9.03
67_F
5000 2360 156.0 45.7
9.05
(19_C)
6000 2830 160.6 47.1
9.06
4000 1890 158.4 46.4
9.05
71_F
5000 2360 165.5 48.5
9.07
(22_C)
6000 2830 170.3 49.9
9.08
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.65
.76
.89
69.5
20.4
4.04
.68
.82
.97
73.3
21.5
4.05
.72
.89
1.00
76.0
22.3
4.06
.52
.62
.72
73.9
21.7
4.05
.54
.65
.78
77.8
22.8
4.06
.56
.69
.85
80.8
23.7
4.07
.40
.50
.60
78.1
22.9
4.06
.42
.52
.63
82.2
24.1
4.07
.42
.54
.67
85.3
25.0
4.08
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.66
.79
.93
127.7 37.4 10.01
.70
.86
1.00
134.1 39.3 10.02
.75
.93
1.00
139.2 40.8 10.04
.53
.64
.75
135.6 39.7 10.02
.55
.67
.82
142.9 41.9 10.04
.57
.72
.89
147.8 43.3 10.05
.41
.51
.61
144.0 42.2 10.04
.42
.54
.65
151.2 44.3 10.07
.43
.56
.70
156.3 45.8 10.07
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.81
.96
72.8
21.3
4.05
.71
.89
1.00
76.3
22.4
4.06
.77
.96
1.00
79.4
23.3
4.07
.54
.65
.77
77.6
22.7
4.06
.56
.69
.85
81.1
23.8
4.07
.59
.74
.92
83.6
24.5
4.08
.41
.52
.63
82.4
24.1
4.07
.42
.55
.67
86.0
25.2
4.09
.43
.58
.72
88.9
26.1
4.09
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.85
1.00
133.5 39.1 10.02
.75
.94
1.00
140.5 41.2 10.03
.81
1.00
1.00
146.2 42.8 10.05
.55
.67
.81
142.4 41.7 10.03
.58
.72
.89
148.5 43.5 10.05
.61
.78
.97
153.3 44.9 10.07
.41
.53
.65
151.6 44.4 10.06
.43
.57
.70
158.0 46.3 10.08
.44
.60
.75
162.7 47.7 10.09
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.65
.77
.91
66.7
19.5
4.49
.69
.84
.98
70.4
20.6
4.50
.73
.91
1.00
73.1
21.4
4.51
.52
.63
.74
71.0
20.8
4.51
.55
.66
.80
74.6
21.9
4.51
.57
.71
.86
77.7
22.8
4.52
.41
.51
.60
75.3
22.1
4.52
.41
.53
.64
79.1
23.2
4.53
.42
.55
.68
81.9
24.0
4.53
Outdoor Air Temperature Entering Outdoor Coil
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.81
.95
120.9 35.4
11.18
.72
.88
1.00
127.3 37.3
11.19
.77
.96
1.00
132.2 38.7
11.19
.53
.64
.77
128.9 37.8
11.17
.56
.69
.84
135.4 39.7
11.19
.58
.74
.91
140.3 41.1
11.21
.41
.52
.62
136.9 40.1
11.19
.42
.54
.66
143.6 42.1
11.21
.43
.57
.71
148.5 43.5
11.23
Outdoor Air Temperature Entering Outdoor Coil
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.83
.98
69.9
20.5
4.50
.73
.91
1.00
73.4
21.5
4.51
.78
.98
1.00
76.4
22.4
4.52
.54
.66
.79
74.6
21.9
4.51
.57
.71
.87
78.0
22.9
4.52
.60
.76
.94
80.3
23.5
4.53
.41
.53
.64
79.2
23.2
4.53
.42
.56
.68
82.8
24.3
4.53
.43
.59
.73
85.2
25.0
4.54
Outdoor Air Temperature Entering Outdoor Coil
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.87
1.00
126.8 37.2
11.18
.76
.96
1.00
133.1 39.0
11.21
.83
1.00
1.00
139.4 40.9
11.21
.56
.68
.83
135.2 39.6
11.20
.59
.74
.92
140.9 41.3
11.21
.62
.80
.99
145.0 42.5
11.24
.41
.54
.66
144.2 42.3
11.23
.43
.58
.71
150.2 44.0
11.24
.45
.61
.77
154.4 45.3
11.25
TS 6 to 20 Ton R−410A Air Conditioners / Page 25
12.5 TON (DUAL CIRCUIT)
AIR HANDLERS
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.66
.79
.93
63.8
18.7
5.01
.70
.86
1.00
67.1
19.7
5.01
.75
.93
1.00
69.6
20.4
5.02
.53
.64
.75
67.8
19.9
5.01
.55
.67
.82
71.4
20.9
5.02
.57
.72
.89
73.9
21.7
5.02
.41
.51
.61
72.0
21.1
5.02
.42
.54
.65
75.6
22.2
5.03
.42
.56
.70
78.2
22.9
5.04
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.84
.98
113.5 33.3 12.50
.74
.91
1.00
119.3 35.0 12.53
.80
.98
1.00
124.0 36.3 12.51
.54
.66
.79
121.4 35.6 12.52
.57
.71
.87
127.0 37.2 12.51
.60
.77
.95
131.4 38.5 12.53
.41
.53
.63
128.7 37.7 12.50
.42
.56
.68
135.0 39.6 12.53
.43
.58
.74
139.8 41.0 12.56
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.85
1.00
66.8
19.6
5.01
.75
.94
1.00
70.2
20.6
5.02
.81
1.00
1.00
73.1
21.4
5.03
.55
.67
.81
71.2
20.9
5.02
.58
.72
.89
74.2
21.7
5.03
.61
.78
.97
76.6
22.4
5.04
.41
.53
.65
75.8
22.2
5.03
.43
.57
.70
79.0
23.2
5.04
.44
.60
.75
81.4
23.9
5.05
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.73
.90
1.00
119.2 34.9 12.52
.79
.99
1.00
125.7 36.8 12.54
.86
1.00
1.00
132.2 38.7 12.53
.57
.70
.86
127.1 37.2 12.54
.60
.76
.95
132.2 38.7 12.53
.63
.83
1.00
136.1 39.9 12.55
.42
.55
.68
135.6 39.7 12.56
.43
.59
.73
141.0 41.3 12.56
.46
.63
.80
145.2 42.6 12.57
[TAA120S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.67
.81
.95
.72
.88
1.00
.77
.96
1.00
.53
.64
.77
.56
.69
.84
.58
.74
.91
.41
.52
.62
.42
.54
.66
.43
.57
.71
[TAA120S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.70
.86
1.00
.77
.95
1.00
.83
1.00
1.00
.55
.68
.82
.58
.73
.91
.61
.80
.98
.42
.53
.65
.43
.57
.70
.43
.60
.77
[TAA150S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.71
.87
1.00
.76
.96
1.00
.83
1.00
1.00
.56
.68
.83
.59
.74
.92
.62
.80
.99
.41
.54
.66
.43
.58
.71
.45
.61
.77
[TAA150S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.75
.94
1.00
.83
1.00
1.00
.90
1.00
1.00
.58
.72
.89
.62
.80
.99
.65
.87
1.00
.43
.56
.70
.44
.60
.77
.47
.65
.84