Lennox T-CLASS TS Series Engineering Data page 19

Split system units
Table of Contents

Advertisement

RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA090S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
2400 1135
87.5
25.6
5.76
63_F
3000 1415 91.7
26.9
5.84
(17_C)
3600 1700 95.1
27.9
5.90
2400 1135
91.7
26.9
5.83
67_F
3000 1415 96.3
28.2
5.92
(19_C)
3600 1700 99.6
29.2
5.98
2400 1135
96.4
28.3
5.92
71_F
3000 1415 100.6 29.5
6.01
(22_C)
3600 1700 104.1 30.5
6.08
COOLING CAPACITY − TSA090S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
2400 1135
86.1
25.2
5.73
63_F
3000 1415 89.9
26.3
5.80
(17_C)
3600 1700 92.7
27.2
5.85
2400 1135
90.7
26.6
5.82
67_F
3000 1415 94.8
27.8
5.89
(19_C)
3600 1700 97.8
28.7
5.95
2400 1135
95.2
27.9
5.90
71_F
3000 1415 99.5
29.2
5.98
(22_C)
3600 1700 102.8 30.1
6.05
COOLING CAPACITY − TSA090S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
2400 1135
87.6
25.7
5.76
63_F
3000 1415 91.7
26.9
5.83
(17_C)
3600 1700 94.9
27.8
5.90
2400 1135
92.4
27.1
5.85
67_F
3000 1415 96.9
28.4
5.93
(19_C)
3600 1700 99.9
29.3
5.99
2400 1135
97.0
28.4
5.94
71_F
3000 1415 101.7 29.8
6.02
(22_C)
3600 1700 105.0 30.8
6.09
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.81
.95
83.8
24.6
6.39
.71
.88
1.00
87.7
25.7
6.46
.76
.95
1.00
90.8
26.6
6.53
.54
.65
.77
87.8
25.7
6.47
.56
.69
.84
92.0
27.0
6.55
.59
.74
.91
95.1
27.9
6.61
.42
.53
.63
92.1
27.0
6.55
.43
.55
.67
96.1
28.2
6.63
.44
.58
.71
99.5
29.2
6.71
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.81
.96
82.2
24.1
6.36
.72
.88
1.00
85.9
25.2
6.43
.77
.95
1.00
88.5
25.9
6.48
.54
.66
.78
86.7
25.4
6.45
.57
.70
.85
90.6
26.6
6.52
.59
.74
.92
93.4
27.4
6.58
.41
.53
.64
91.1
26.7
6.53
.42
.56
.68
95.2
27.9
6.61
.44
.58
.72
98.0
28.7
6.67
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.81
.95
83.7
24.5
6.39
.71
.88
1.00
87.6
25.7
6.46
.76
.95
1.00
90.6
26.6
6.52
.54
.65
.77
88.4
25.9
6.48
.56
.69
.84
92.5
27.1
6.56
.59
.74
.92
95.4
28.0
6.62
.42
.52
.63
92.9
27.2
6.57
.42
.55
.67
97.2
28.5
6.66
.44
.58
.71
100.3 29.4
6.72
Outdoor Air Temperature Entering Outdoor Coil
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.83
.97
79.7
23.4
7.11
.73
.90
1.00
83.4
24.4
7.19
.78
.98
1.00
86.3
25.3
7.24
.55
.66
.79
83.7
24.5
7.19
.57
.71
.87
87.6
25.7
7.27
.60
.76
.94
90.5
26.5
7.32
.42
.53
.64
87.9
25.8
7.28
.43
.56
.69
91.6
26.8
7.35
.44
.59
.73
94.7
27.8
7.42
Outdoor Air Temperature Entering Outdoor Coil
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.83
.98
78.3
22.9
7.08
.74
.91
1.00
81.6
23.9
7.15
.79
.98
1.00
84.3
24.7
7.20
.55
.67
.80
82.6
24.2
7.17
.58
.71
.87
86.0
25.2
7.24
.60
.76
.95
88.5
25.9
7.29
.42
.54
.65
86.8
25.4
7.26
.43
.57
.69
90.5
26.5
7.33
.44
.59
.74
93.2
27.3
7.39
Outdoor Air Temperature Entering Outdoor Coil
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.83
.98
79.7
23.4
7.11
.73
.91
1.00
83.4
24.4
7.19
.78
.98
1.00
85.7
25.1
7.23
.54
.66
.79
84.1
24.6
7.20
.57
.71
.87
87.9
25.8
7.28
.60
.76
.94
90.4
26.5
7.33
.42
.53
.64
88.4
25.9
7.29
.43
.56
.69
92.5
27.1
7.38
.44
.59
.74
95.2
27.9
7.43
TS 6 to 20 Ton R−410A Air Conditioners / Page 19
UP−FLOW INDOOR COIL
[(2) CX34−49C−6F]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.85
1.00
75.3
22.1
7.94
.75
.93
1.00
78.7
23.1
8.01
.81
1.00
1.00
81.9
24.0
8.08
.55
.68
.81
79.2
23.2
8.02
.58
.73
.90
82.8
24.3
8.09
.61
.78
.97
85.3
25.0
8.15
.42
.55
.65
83.0
24.3
8.10
.44
.57
.70
86.5
25.4
8.18
.45
.60
.76
89.2
26.1
8.23
DOWN−FLOW INDOOR COILS
[(2) CR33−50/60C−F]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.86
1.00
73.8
21.6
7.91
.76
.94
1.00
76.8
22.5
7.97
.81
.99
1.00
80.1
23.5
8.04
.56
.68
.82
78.0
22.9
7.99
.59
.73
.90
81.2
23.8
8.07
.61
.79
.97
83.3
24.4
8.11
.41
.55
.66
82.1
24.1
8.09
.43
.58
.71
85.5
25.1
8.16
.45
.61
.76
87.7
25.7
8.19
HORIZONTAL INDOOR COILS
[(2) CH33−49C−2F]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.85
1.00
75.1
22.0
7.93
.75
.93
1.00
78.5
23.0
8.01
.80
1.00
1.00
81.6
23.9
8.07
.55
.67
.81
79.6
23.3
8.03
.58
.73
.90
82.8
24.3
8.10
.60
.78
.97
85.0
24.9
8.14
.42
.54
.65
83.7
24.5
8.12
.43
.57
.70
87.2
25.6
8.20
.45
.60
.76
89.6
26.3
8.24
7.5 TON
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.72
.88
1.00
.78
.97
1.00
.84
1.00
1.00
.56
.69
.84
.60
.75
.93
.62
.81
1.00
.42
.55
.67
.44
.59
.73
.45
.62
.79
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.72
.89
1.00
.78
.97
1.00
.84
1.00
1.00
.57
.70
.85
.60
.76
.94
.63
.82
1.00
.42
.55
.68
.44
.59
.73
.45
.62
.79
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.71
.88
1.00
.78
.97
1.00
.84
1.00
1.00
.56
.69
.84
.59
.75
.93
.62
.81
1.00
.42
.55
.67
.44
.58
.73
.45
.61
.79

Hide quick links: