Lennox T-CLASS TS Series Engineering Data page 18

Split system units
Table of Contents

Advertisement

RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA090S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
2400 1135
88.5
25.9
5.78
63_F
3000 1415 92.7
27.2
5.86
(17_C)
3600 1700 95.8
28.1
5.91
2400 1135
93.5
27.4
5.87
67_F
3000 1415 97.5
28.6
5.95
(19_C)
3600 1700 100.7 29.5
6.01
2400 1135
98.5
28.9
5.97
71_F
3000 1415 102.7 30.1
6.04
(22_C)
3600 1700 105.8 31.0
6.10
COOLING CAPACITY − TSA090S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
2400 1135
89.7
26.3
5.80
63_F
3000 1415 93.9
27.5
5.88
(17_C)
3600 1700 97.0
28.4
5.94
2400 1135
94.9
27.8
5.89
67_F
3000 1415 99.3
29.1
5.98
(19_C)
3600 1700 102.1 29.9
6.03
2400 1135 100.0 29.3
5.99
71_F
3000 1415 104.9 30.7
6.09
(22_C)
3600 1700 107.6 31.5
6.15
COOLING CAPACITY − (2) TSA090S4S (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
4800 2265 91.2
26.7
4.63
63_F
6000 2830 95.6
28.0
4.70
(17_C)
7200 3400 98.6
28.9
4.76
4800 2265 95.9
28.1
4.71
67_F
6000 2830 100.5 29.5
4.79
(19_C)
7200 3400 103.7 30.4
4.85
4800 2265 100.5 29.5
4.79
71_F
6000 2830 105.2 30.8
4.88
(22_C)
7200 3400 108.6 31.8
4.94
COOLING CAPACITY − (2) TSA090S4S (SECOND STAGE) with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
4800 2265 169.3 49.6
11.38
63_F
6000 2830 176.9 51.8
11.51
(17_C)
7200 3400 182.4 53.5
11.62
4800 2265 178.2 52.2
11.54
67_F
6000 2830 186.1 54.5
11.68
(19_C)
7200 3400 191.7 56.2
11.79
4800 2265 186.7 54.7
11.70
71_F
6000 2830 194.9 57.1
11.86
(22_C)
7200 3400 200.8 58.8
11.97
TS 6 to 20 Ton R−410A Air Conditioners / Page 18
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.82
.97
84.7
24.8
6.40
.73
.90
1.00
88.5
25.9
6.48
.79
.97
1.00
91.3
26.8
6.54
.54
.65
.78
89.6
26.3
6.50
.57
.70
.86
93.4
27.4
6.58
.60
.76
.94
95.8
28.1
6.63
.41
.52
.63
94.2
27.6
6.59
.43
.55
.69
98.2
28.8
6.68
.44
.59
.74
100.7 29.5
6.72
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.82
.97
85.6
25.1
6.43
.73
.91
1.00
89.5
26.2
6.50
.78
.98
1.00
92.7
27.2
6.56
.54
.65
.78
90.8
26.6
6.52
.57
.71
.87
94.8
27.8
6.60
.60
.76
.95
97.3
28.5
6.66
.41
.52
.63
95.6
28.0
6.63
.42
.56
.69
99.8
29.2
6.71
.44
.59
.73
102.3 30.0
6.77
Outdoor Air Temperature Entering Outdoor Coil
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.79
.93
88.1
25.8
5.13
.71
.86
1.00
92.2
27.0
5.20
.75
.93
1.00
95.1
27.9
5.25
.53
.64
.76
92.7
27.2
5.21
.56
.68
.83
96.9
28.4
5.29
.58
.72
.89
99.9
29.3
5.34
.42
.52
.62
97.2
28.5
5.29
.42
.54
.66
101.6 29.8
5.37
.43
.57
.70
104.6 30.7
5.43
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.83
.97
161.7 47.4 12.63
.73
.90
1.00
168.8 49.5 12.77
.78
.97
1.00
174.3 51.1 12.87
.54
.66
.79
170.4 49.9 12.81
.57
.71
.87
177.4 52.0 12.93
.60
.76
.94
182.5 53.5 13.03
.42
.53
.64
178.7 52.4 12.96
.42
.56
.69
186.2 54.6 13.11
.44
.59
.73
191.8 56.2 13.22
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.84
.99
80.6
23.6
7.13
.75
.93
1.00
84.0
24.6
7.20
.80
.99
1.00
87.0
25.5
7.26
.54
.67
.80
85.3
25.0
7.22
.58
.72
.89
88.6
26.0
7.29
.60
.78
.97
91.1
26.7
7.34
.42
.53
.65
89.8
26.3
7.32
.43
.57
.70
93.3
27.3
7.39
.44
.59
.75
95.6
28.0
7.44
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.84
.99
81.4
23.9
7.14
.75
.94
1.00
85.1
24.9
7.22
.81
1.00
1.00
88.7
26.0
7.30
.55
.67
.80
86.0
25.2
7.24
.58
.72
.90
89.8
26.3
7.32
.61
.78
.98
92.3
27.1
7.37
.42
.53
.65
90.9
26.6
7.34
.43
.57
.70
94.8
27.8
7.42
.44
.59
.76
97.4
28.5
7.48
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.81
.95
84.6
24.8
5.69
.72
.88
1.00
88.4
25.9
5.76
.76
.95
1.00
91.2
26.7
5.81
.54
.65
.77
89.1
26.1
5.77
.56
.69
.85
93.1
27.3
5.84
.59
.74
.91
95.9
28.1
5.90
.42
.52
.63
93.4
27.4
5.85
.42
.55
.67
97.5
28.6
5.93
.43
.58
.72
100.4 29.4
5.98
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.85
.99
154.1 45.2 14.09
.75
.93
1.00
160.4 47.0 14.21
.80
.99
1.00
165.3 48.4 14.31
.55
.67
.81
161.9 47.4 14.23
.58
.72
.89
168.8 49.5 14.37
.61
.78
.96
173.3 50.8 14.47
.42
.54
.65
170.0 49.8 14.40
.43
.57
.70
176.9 51.8 14.55
.45
.60
.76
182.1 53.4 14.64
AIR HANDLERS
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.87
1.00
76.1
22.3
7.95
.77
.96
1.00
79.1
23.2
8.02
.83
1.00
1.00
82.5
24.2
8.10
.56
.69
.83
80.3
23.5
8.04
.59
.74
.92
83.3
24.4
8.11
.62
.81
.99
85.8
25.1
8.16
.42
.54
.66
84.8
24.9
8.15
.43
.58
.72
87.8
25.7
8.20
.45
.61
.78
90.2
26.4
8.26
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.87
1.00
76.8
22.5
7.97
.77
.97
1.00
80.1
23.5
8.04
.83
1.00
1.00
84.1
24.6
8.13
.55
.68
.83
81.5
23.9
8.07
.59
.75
.93
84.4
24.7
8.13
.62
.81
1.00
87.0
25.5
8.19
.42
.54
.67
85.8
25.1
8.17
.43
.58
.72
89.1
26.1
8.24
.45
.62
.79
91.5
26.8
8.29
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.83
.97
80.8
23.7
6.32
.73
.90
1.00
84.4
24.7
6.39
.78
.97
1.00
87.1
25.5
6.44
.54
.66
.79
85.2
25.0
6.40
.57
.71
.87
88.7
26.0
6.47
.60
.76
.94
91.3
26.8
6.52
.42
.53
.64
89.3
26.2
6.48
.42
.56
.69
93.1
27.3
6.55
.44
.59
.73
95.9
28.1
6.61
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.87
1.00
145.2 42.6 15.75
.77
.95
1.00
151.1 44.3 15.84
.83
1.00
1.00
157.0 46.0 15.97
.56
.69
.83
152.9 44.8 15.90
.59
.74
.92
158.9 46.6 16.03
.62
.81
.99
163.1 47.8
16.11
.42
.55
.67
160.6 47.1 16.04
.44
.58
.72
167.1 49.0 16.19
.45
.61
.78
171.3 50.2 16.27
7.5 TON
[TAA090S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.73
.90
1.00
.79
.99
1.00
.86
1.00
1.00
.57
.70
.86
.60
.77
.95
.64
.84
1.00
.42
.56
.68
.44
.58
.74
.45
.63
.81
[TAA120S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.73
.90
1.00
.79
1.00
1.00
.87
1.00
1.00
.56
.71
.86
.60
.77
.96
.63
.85
1.00
.42
.55
.68
.43
.59
.74
.46
.63
.82
[TAA180S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.70
.85
.99
.75
.93
1.00
.80
.99
1.00
.55
.67
.81
.58
.72
.89
.61
.78
.96
.42
.54
.65
.43
.57
.70
.45
.60
.76
[TAA180S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.73
.90
1.00
.80
.99
1.00
.86
1.00
1.00
.57
.71
.87
.60
.77
.95
.64
.84
1.00
.43
.56
.69
.44
.59
.75
.45
.63
.82