RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA120S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 113.3 33.2
7.09
63_F
4000 1890 118.5 34.7
7.18
(17_C)
4800 2265 122.2 35.8
7.25
3200 1510 120.0 35.2
7.21
67_F
4000 1890 124.8 36.6
7.30
(19_C)
4800 2265 128.5 37.7
7.37
3200 1510 126.2 37.0
7.33
71_F
4000 1890 131.3 38.5
7.42
(22_C)
4800 2265 135.0 39.6
7.51
COOLING CAPACITY − (2) TSA120S4S (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
6400 3020 120.0 35.2
5.69
63_F
8000 3775 125.6 36.8
5.79
(17_C)
9600 4530 129.1 37.8
5.86
6400 3020 126.8 37.2
5.81
67_F
8000 3775 132.5 38.8
5.91
(19_C)
9600 4530 136.6 40.0
5.99
6400 3020 133.4 39.1
5.93
71_F
8000 3775 139.1 40.8
6.04
(22_C)
9600 4530 143.4 42.0
6.12
COOLING CAPACITY − (2) TSA120S4S (SECOND STAGE) with
85_F (29_C)
Total
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 185.0 54.2 13.53
63_F
8000 3775 232.7 68.2 14.29
(17_C)
4800 2265 208.9 61.2 13.90
3200 1510 196.5 57.6 13.69
67_F
8000 3775 245.7 72.0 14.53
(19_C)
4800 2265 221.0 64.8 14.09
3200 1510 207.7 60.9 13.87
71_F
8000 3775 258.1 75.6 14.76
(22_C)
4800 2265 232.6 68.2 14.30
COOLING CAPACITY − TSA120S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 110.8 32.5
7.05
63_F
4000 1890 116.2 34.1
7.15
(17_C)
4800 2265 120.2 35.2
7.21
3200 1510 116.7 34.2
7.16
67_F
4000 1890 122.0 35.8
7.24
(19_C)
4800 2265 126.0 36.9
7.33
3200 1510 123.1 36.1
7.27
71_F
4000 1890 128.6 37.7
7.37
(22_C)
4800 2265 132.7 38.9
7.45
TS 6 to 20 Ton R−410A Air Conditioners / Page 20
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.86
.99
108.4 31.8
7.90
.77
.94
1.00
113.2 33.2
7.99
.82
1.00
1.00
117.2 34.3
8.06
.56
.69
.82
114.8 33.6
8.01
.60
.75
.91
119.5 35.0
8.10
.63
.80
.98
122.3 35.8
8.16
.43
.55
.67
121.1 35.5
8.13
.44
.58
.72
125.6 36.8
8.23
.45
.62
.78
128.9 37.8
8.29
Outdoor Air Temperature Entering Outdoor Coil
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.82
.96
116.1 34.0
6.35
.73
.89
1.00
121.0 35.5
6.43
.78
.96
1.00
124.6 36.5
6.50
.55
.67
.79
122.5 35.9
6.46
.58
.71
.86
127.8 37.5
6.55
.60
.77
.93
131.2 38.5
6.62
.43
.54
.64
128.7 37.7
6.57
.43
.56
.69
134.1 39.3
6.67
.45
.60
.74
137.9 40.4
6.75
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.62
.71
.79
178.4 52.3 15.19
.77
.94
1.00
221.5 64.9 15.89
.67
.78
.89
200.2 58.7 15.52
.51
.60
.67
189.6 55.6 15.36
.60
.74
.90
234.4 68.7 16.13
.54
.64
.74
212.3 62.2 15.72
.42
.49
.57
200.5 58.8 15.53
.44
.58
.72
246.3 72.2 16.35
.42
.52
.62
223.8 65.6 15.93
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.84
.97
106.3 31.2
7.86
.74
.90
1.00
111.2 32.6
7.95
.79
.97
1.00
114.9 33.7
8.01
.56
.68
.80
111.8 32.8
7.96
.58
.72
.87
116.8 34.2
8.05
.61
.77
.94
120.5 35.3
8.12
.43
.54
.66
117.9 34.6
8.07
.44
.57
.70
123.1 36.1
8.17
.45
.60
.75
126.7 37.1
8.24
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.73
.88
1.00
103.1 30.2
8.82
.79
.96
1.00
107.6 31.5
8.90
.84
1.00
1.00
112.3 32.9
8.98
.58
.70
.84
109.3 32.0
8.93
.60
.76
.93
113.3 33.2
9.00
.64
.82
1.00
116.2 34.1
9.06
.43
.56
.68
114.9 33.7
9.03
.44
.59
.74
119.6 35.1
9.12
.46
.63
.80
122.5 35.9
9.18
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.84
.98
111.7 32.7
7.06
.75
.92
1.00
116.4 34.1
7.14
.80
.98
1.00
120.0 35.2
7.21
.56
.68
.80
117.8 34.5
7.18
.58
.73
.88
122.8 36.0
7.26
.61
.78
.95
126.1 37.0
7.33
.43
.54
.65
124.0 36.3
7.28
.44
.57
.70
129.1 37.8
7.38
.45
.60
.75
132.3 38.8
7.45
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.63
.71
.81
170.9 50.1 17.08
.78
.96
1.00
211.4 62.0 17.74
.67
.79
.92
190.9 55.9 17.39
.52
.60
.68
181.5 53.2 17.23
.60
.76
.93
223.4 65.5 17.94
.54
.65
.75
202.2 59.3 17.56
.41
.50
.57
192.1 56.3 17.40
.44
.59
.74
234.9 68.8 18.17
.42
.53
.62
213.3 62.5 17.76
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.85
.99
101.3 29.7
8.79
.76
.93
1.00
106.0 31.1
8.87
.81
.99
1.00
109.3 32.0
8.93
.56
.69
.82
106.5 31.2
8.88
.59
.73
.89
111.2 32.6
8.96
.62
.79
.96
114.6 33.6
9.03
.43
.55
.67
112.4 32.9
8.99
.44
.58
.72
117.2 34.3
9.08
.46
.61
.77
120.5 35.3
9.14
AIR HANDLERS
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.74
.90
1.00
97.4
28.5
9.86
.81
.99
1.00
101.6 29.8
9.93
.87
1.00
1.00
106.6 31.2 10.03
.58
.72
.87
102.9 30.2
9.96
.62
.78
.96
106.6 31.2 10.03
.65
.84
1.00
109.3 32.0 10.07
.43
.57
.70
108.5 31.8 10.06
.45
.61
.76
112.5 33.0 10.13
.46
.64
.82
115.2 33.8 10.19
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.86
.99
106.7 31.3
7.87
.77
.94
1.00
110.7 32.4
7.95
.82
1.00
1.00
114.7 33.6
8.01
.57
.69
.82
112.7 33.0
7.97
.60
.74
.90
117.2 34.3
8.06
.63
.80
.97
120.6 35.3
8.12
.43
.55
.67
118.6 34.8
8.09
.44
.58
.72
123.1 36.1
8.18
.45
.61
.78
126.7 37.1
8.25
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.63
.72
.82
162.4 47.6 19.23
.80
.99
1.00
199.4 58.4 19.79
.68
.81
.94
181.2 53.1 19.51
.52
.61
.69
172.5 50.6 19.38
.62
.78
.95
210.5 61.7 20.00
.55
.66
.77
191.7 56.2 19.68
.42
.50
.58
182.3 53.4 19.53
.45
.61
.76
221.7 65.0 20.22
.42
.53
.64
201.9 59.2 19.84
UP−FLOW INDOOR COIL
[(2) CX34−62D−6F]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.73
.88
1.00
95.9
28.1
9.84
.78
.95
1.00
100.1 29.3
9.91
.83
1.00
1.00
103.9 30.5
9.98
.57
.70
.84
100.6 29.5
9.91
.60
.75
.92
105.1 30.8 10.00
.63
.81
.99
108.0 31.7 10.05
.44
.56
.68
106.5 31.2 10.03
.45
.59
.73
110.6 32.4 10.10
.46
.63
.79
113.5 33.3 10.15
10 TON
[TAA120S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.76
.93
1.00
.83
1.00
1.00
.90
1.00
1.00
.59
.74
.90
.63
.81
.99
.67
.88
1.00
.44
.58
.71
.46
.62
.79
.47
.67
.86
[TAA240S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.72
.88
1.00
.78
.96
1.00
.84
1.00
1.00
.57
.70
.84
.60
.76
.93
.64
.82
.99
.43
.55
.68
.44
.59
.74
.45
.63
.80
[TAA240S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.64
.74
.84
.83
1.00
1.00
.70
.83
.97
.52
.61
.70
.63
.81
.99
.55
.67
.79
.41
.50
.59
.46
.62
.78
.43
.54
.65
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.74
.90
1.00
.80
.99
1.00
.86
1.00
1.00
.58
.72
.87
.62
.78
.95
.65
.84
1.00
.44
.57
.70
.45
.61
.76
.47
.64
.82