Lennox T-CLASS TS Series Engineering Data page 22

Split system units
Table of Contents

Advertisement

RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA120S4D (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 61.7
18.1
2.72
63_F
4000 1890 64.7
19.0
2.76
(17_C)
4800 2265 66.9
19.6
2.79
3200 1510 65.3
19.1
2.77
67_F
4000 1890 68.5
20.1
2.80
(19_C)
4800 2265 70.6
20.7
2.83
3200 1510 68.9
20.2
2.81
71_F
4000 1890 72.2
21.2
2.84
(22_C)
4800 2265 74.4
21.8
2.87
COOLING CAPACITY − TSA120S4D (SECOND STAGE) with
85_F (29_C)
Total
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 113.6 33.3
6.99
63_F
4000 1890 118.9 34.8
7.04
(17_C)
4800 2265 123.1 36.1
7.10
3200 1510 120.5 35.3
7.06
67_F
4000 1890 125.6 36.8
7.12
(19_C)
4800 2265 129.6 38.0
7.18
3200 1510 127.0 37.2
7.15
71_F
4000 1890 132.4 38.8
7.22
(22_C)
4800 2265 136.5 40.0
7.29
COOLING CAPACITY − TSA120S4D (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 59.2
17.3
2.70
63_F
4000 1890 62.3
18.3
2.73
(17_C)
4800 2265 64.7
19.0
2.76
3200 1510 62.7
18.4
2.74
67_F
4000 1890 65.7
19.3
2.77
(19_C)
4800 2265 68.1
20.0
2.80
3200 1510 66.2
19.4
2.78
71_F
4000 1890 69.5
20.4
2.81
(22_C)
4800 2265 71.9
21.1
2.84
COOLING CAPACITY − TSA120S4D (SECOND STAGE) with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 109.8 32.2
6.94
63_F
4000 1890 115.1 33.7
7.00
(17_C)
4800 2265 119.2 34.9
7.04
3200 1510 116.1 34.0
7.01
67_F
4000 1890 121.5 35.6
7.06
(19_C)
4800 2265 125.0 36.6
7.13
3200 1510 122.7 36.0
7.10
71_F
4000 1890 128.4 37.6
7.16
(22_C)
4800 2265 132.4 38.8
7.23
TS 6 to 20 Ton R−410A Air Conditioners / Page 22
Outdoor Air Temperature Entering Outdoor Coil
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.65
.78
.94
59.4
17.4
3.08
.69
.87
1.00
62.1
18.2
3.11
.74
.95
1.00
64.3
18.8
3.14
.52
.62
.74
62.8
18.4
3.12
.54
.67
.82
65.7
19.3
3.16
.56
.71
.91
67.8
19.9
3.19
.40
.50
.60
66.3
19.4
3.17
.41
.53
.65
69.3
20.3
3.21
.41
.55
.69
71.5
21.0
3.24
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.82
.99
108.2 31.7
7.91
.72
.92
1.00
113.1 33.1
7.95
.78
.99
1.00
117.3 34.4
8.02
.53
.64
.78
114.9 33.7
7.99
.56
.69
.87
119.7 35.1
8.06
.59
.76
.96
123.2 36.1
8.09
.40
.51
.62
121.3 35.5
8.08
.41
.54
.67
126.5 37.1
8.15
.42
.58
.73
129.9 38.1
8.21
Outdoor Air Temperature Entering Outdoor Coil
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.64
.77
.91
57.1
16.7
3.06
.67
.83
.99
60.0
17.6
3.09
.71
.89
1.00
62.2
18.2
3.12
.52
.62
.73
60.5
17.7
3.10
.53
.65
.79
63.4
18.6
3.13
.55
.69
.85
65.4
19.2
3.16
.40
.50
.59
63.8
18.7
3.14
.41
.52
.63
67.0
19.6
3.18
.42
.54
.67
69.2
20.3
3.21
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.66
.80
.96
104.9 30.7
7.86
.70
.88
1.00
109.8 32.2
7.93
.75
.95
1.00
113.6 33.3
7.97
.53
.63
.76
111.0 32.5
7.93
.55
.67
.84
115.9 34.0
8.01
.57
.72
.91
119.5 35.0
8.05
.40
.51
.61
117.3 34.4
8.02
.41
.53
.66
122.3 35.8
8.08
.42
.56
.70
126.2 37.0
8.16
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.66
.80
.96
56.8
16.6
3.49
.70
.89
1.00
59.4
17.4
3.52
.76
.97
1.00
61.6
18.1
3.55
.52
.63
.75
60.2
17.6
3.53
.55
.68
.84
62.8
18.4
3.56
.57
.73
.93
64.8
19.0
3.59
.40
.51
.61
63.5
18.6
3.57
.41
.54
.66
66.2
19.4
3.61
.42
.56
.71
68.3
20.0
3.64
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.85
1.00
102.5 30.0
8.99
.74
.95
1.00
107.3 31.4
9.03
.81
1.00
1.00
112.0 32.8
9.11
.54
.66
.80
108.8 31.9
9.06
.57
.71
.91
113.3 33.2
9.12
.60
.78
.99
116.3 34.1
9.16
.40
.52
.64
114.8 33.6
9.15
.41
.56
.69
119.4 35.0
9.22
.43
.59
.75
122.7 36.0
9.27
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.65
.78
.93
54.9
16.1
3.47
.68
.85
1.00
57.5
16.9
3.50
.73
.92
1.00
59.6
17.5
3.52
.52
.63
.74
58.1
17.0
3.50
.54
.66
.81
60.8
17.8
3.53
.56
.69
.88
62.5
18.3
3.56
.40
.50
.60
61.4
18.0
3.55
.41
.53
.64
64.2
18.8
3.58
.42
.55
.67
66.2
19.4
3.61
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.82
.99
99.5
29.2
8.94
.72
.91
1.00
104.1 30.5
8.99
.77
.99
1.00
107.6 31.5
9.05
.53
.65
.78
105.5 30.9
9.02
.56
.69
.86
109.8 32.2
9.08
.58
.75
.95
112.9 33.1
9.12
.41
.52
.62
111.3 32.6
9.07
.42
.54
.67
116.1 34.0
9.16
.43
.57
.72
119.5 35.0
9.21
10 TON (DUAL CIRCUIT)
AIR HANDLERS
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.67
.82
.99
54.2
15.9
3.95
.72
.92
1.00
56.6
16.6
3.97
.78
.99
1.00
58.7
17.2
4.01
.53
.64
.78
57.5
16.9
3.99
.55
.69
.87
59.9
17.6
4.03
.59
.76
.96
61.6
18.1
4.04
.40
.51
.62
60.7
17.8
4.04
.41
.54
.67
63.2
18.5
4.07
.42
.58
.73
65.0
19.0
4.10
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.88
1.00
96.4
28.3 10.22
.77
.98
1.00
100.8 29.5 10.28
.84
1.00
1.00
105.6 30.9 10.37
.54
.68
.84
102.4 30.0 10.30
.58
.74
.94
105.9 31.0 10.34
.61
.81
1.00
108.8 31.9 10.38
.41
.53
.65
108.0 31.7 10.39
.42
.57
.71
112.1 32.9 10.45
.43
.60
.78
115.1 33.7 10.52
UP−FLOW INDOOR COIL
[(2) CX34−60D−6F]
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.66
.80
.96
52.5
15.4
3.93
.70
.88
1.00
54.9
16.1
3.96
.75
.95
1.00
56.8
16.6
3.98
.53
.63
.76
55.5
16.3
3.96
.55
.67
.84
58.0
17.0
4.00
.57
.72
.91
59.8
17.5
4.02
.40
.51
.61
58.6
17.2
4.01
.41
.53
.66
61.2
17.9
4.04
.42
.56
.70
63.1
18.5
4.08
[(2) CX34−60D−6F]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.85
1.00
93.8
27.5 10.20
.74
.94
1.00
98.1
28.8 10.24
.80
1.00
1.00
101.9 29.9 10.30
.54
.66
.81
99.3
29.1 10.28
.57
.71
.90
103.2 30.2 10.33
.59
.77
.98
106.3 31.2 10.35
.41
.52
.64
105.0 30.8 10.35
.42
.56
.69
109.1 32.0 10.40
.43
.59
.75
112.1 32.9 10.43
[TAA120S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.68
.85
1.00
.74
.95
1.00
.81
1.00
1.00
.54
.66
.80
.57
.71
.91
.59
.78
.99
.40
.52
.64
.41
.56
.69
.43
.59
.75
[TAA120S4D]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.72
.92
1.00
.80
1.00
1.00
.88
1.00
1.00
.56
.70
.87
.59
.77
.98
.63
.85
1.00
.41
.54
.67
.43
.58
.75
.44
.63
.83
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.67
.82
.99
.72
.91
1.00
.77
.99
1.00
.53
.65
.78
.56
.69
.86
.58
.74
.95
.41
.52
.62
.42
.54
.67
.43
.57
.72
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.70
.89
1.00
.77
.98
1.00
.84
1.00
1.00
.55
.68
.85
.58
.74
.94
.61
.81
1.00
.41
.54
.66
.43
.57
.72
.44
.60
.78