Lennox T-CLASS TS Series Engineering Data page 24

Split system units
Table of Contents

Advertisement

RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA120S4D (FIRST STAGE) with
Total
65_F (18_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Temperat
Motor
Capacity
ure
kW
Input
cfm
L/s kBtuh kW
3200 1510 59.2
17.3
2.70
63_F
4000 1890 62.4
18.3
2.73
(17_C)
4800 2265 64.8
19.0
2.76
3200 1510 62.4
18.3
2.73
67_F
4000 1890 65.7
19.3
2.77
(19_C)
4800 2265 68.3
20.0
2.80
3200 1510 65.7
19.3
2.77
71_F
4000 1890 69.3
20.3
2.81
(22_C)
4800 2265 71.8
21.0
2.84
COOLING CAPACITY − TSA120S4D (SECOND STAGE) with
85_F (29_C)
Total
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
3200 1510 109.7 32.1
6.94
63_F
4000 1890 115.2 33.8
6.99
(17_C)
4800 2265 119.1 34.9
7.04
3200 1510 115.4 33.8
6.99
67_F
4000 1890 121.4 35.6
7.08
(19_C)
4800 2265 125.6 36.8
7.13
3200 1510 121.9 35.7
7.08
71_F
4000 1890 127.9 37.5
7.16
(22_C)
4800 2265 132.2 38.7
7.23
TS 6 to 20 Ton R−410A Air Conditioners / Page 24
Outdoor Air Temperature Entering Outdoor Coil
75_F (24_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.64
.76
.89
57.1
16.7
3.06
.67
.82
.98
60.0
17.6
3.09
.70
.88
1.00
62.3
18.3
3.12
.51
.61
.72
60.1
17.6
3.09
.53
.64
.78
63.1
18.5
3.13
.55
.68
.84
65.6
19.2
3.16
.40
.50
.59
63.5
18.6
3.13
.41
.52
.62
66.7
19.5
3.17
.42
.54
.66
69.1
20.3
3.20
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.65
.79
.94
104.9 30.7
7.86
.69
.86
1.00
110.0 32.2
7.93
.73
.93
1.00
113.6 33.3
7.96
.52
.63
.75
110.3 32.3
7.91
.54
.67
.82
115.8 33.9
8.00
.56
.71
.89
119.7 35.1
8.05
.40
.51
.61
116.6 34.2
8.00
.41
.53
.65
121.8 35.7
8.08
.42
.55
.68
126.0 36.9
8.15
85_F (29_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.64
.77
.92
54.9
16.1
3.47
.68
.84
1.00
57.6
16.9
3.49
.72
.90
1.00
59.6
17.5
3.52
.52
.62
.73
57.7
16.9
3.49
.54
.66
.80
60.7
17.8
3.54
.56
.69
.86
62.8
18.4
3.56
.40
.50
.60
61.0
17.9
3.54
.41
.52
.63
64.0
18.8
3.58
.42
.54
.67
66.1
19.4
3.61
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.66
.81
.97
99.5
29.2
8.94
.71
.89
1.00
104.1 30.5
9.01
.76
.96
1.00
107.6 31.5
9.03
.53
.64
.77
104.9 30.7
9.00
.55
.68
.85
110.0 32.2
9.08
.58
.73
.92
113.4 33.2
9.12
.41
.51
.62
110.7 32.4
9.09
.42
.54
.66
115.7 33.9
9.17
.43
.56
.70
119.4 35.0
9.21
10 TON (DUAL CIRCUIT)
HORIZONTAL INDOOR COILS
[(2) CH33−62D−2F]
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.65
.79
.94
52.5
15.4
3.93
.69
.86
1.00
55.0
16.1
3.96
.73
.93
1.00
56.8
16.6
3.98
.52
.63
.75
55.2
16.2
3.95
.54
.67
.82
57.9
17.0
3.99
.56
.71
.89
59.9
17.6
4.02
.40
.51
.61
58.3
17.1
4.00
.41
.53
.65
60.9
17.8
4.04
.42
.55
.68
63.0
18.5
4.07
[(2) CH33−62D−2F]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.84
1.00
93.8
27.5 10.20
.73
.92
1.00
97.9
28.7 10.24
.78
.99
1.00
101.2 29.7 10.27
.54
.65
.80
98.6
28.9 10.27
.56
.70
.88
103.3 30.3 10.34
.59
.76
.96
106.5 31.2 10.36
.41
.52
.63
104.4 30.6 10.34
.42
.55
.68
108.9 31.9 10.42
.43
.58
.73
112.2 32.9 10.47
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.66
.81
.97
.71
.89
1.00
.76
.96
1.00
.53
.64
.77
.55
.68
.85
.58
.73
.92
.41
.51
.62
.42
.54
.66
.43
.56
.70
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.69
.87
1.00
.76
.96
1.00
.82
1.00
1.00
.55
.67
.83
.57
.73
.92
.60
.79
1.00
.41
.53
.65
.43
.56
.70
.44
.59
.76

Hide quick links: