SMART CONTROLLER

INTRODUCTION

The smart controller is a parametric controller for the complete management of air conditioners. All settings
are pre-pr ogrammed at the factory. Cooling setpoint, cooling differential, high/low temperature alarm setpoints,
and door open and/or smoke detected switch can be adjusted by the user. Alarms are outputted through a relay
contact.
NOTE: The polyester tape on the topside and the neoprene seal around the connectors
assure IP34 rating protection for the controller. DO NOT REMOVE.

ENERGIZING THE CONTROLLER

The controller is wired and pre-pr ogrammed at the factory to be energizing when power is applied to the air
conditioner. The controller will default to the standalone operating mode when initially powered on. Master/Slave
operating mode is optional and will require additional setup.

CONTROL STATUS INDICATION

The display has numerous symbols that indicate if the controller is heating, cooling, alarming; if the compressor
is enabled and if the ambient fan is enabled. The 3 alpha-numeric characters further describe alarms and show
the cabinet temperature by default.
NOTE: The Slim Fit air conditioners DO NOT come standard with a heating option.
SYMBOL
1,2,3,4
A
B
C
D
E
F
G
H
NOTE: On the smart controller, the display symbols for "H" and "E" are always OFF. If they turn
ON, simply hold the
symbol is required to minimize the heating setpoint (parameter A04) and/or defrost setpoint
(parameter A01). Then, hold the
snowflake symbol ("G").
C-NET INDUSTRIAL LTD. | +44(0)121 544 8608 | INFO@CNET-IS.CO.UK | WWW.CNET-IS.CO.UK
89116616
COLOR
ICON ON
1. Compressor On
AMBER
2. TLAN Device ID
AMBER
Compressor On
AMBER
Evaporator Fan On
AMBER
Not Used
AMBER
Master Unit
AMBER
Electric Heater
RED
Alarm Active
AMBER
Controller Active
AMBER
Not Used
"sun" button greater than 5 seconds to turn OFF. The electric heater "E"
ICON FLASHING
1. Flashing at startup request in standalone mode.
2. Master/Slave Mode: 1: TLAN Master. 2,3,4: TLAN
Device ID 2,3,4 are not active in standalone mode.
Active when compressor is ON
Active when evaporator fan is ON
Not used and always OFF
Active when this is the TLAN Master
Not used (always OFF)
Active if there is an alarm condition
ON indicates power and activates all functions.
OFF indicates controller is in standby mode and all
functions are OFF.
Not used (always OFF)
"Cooling" button greater than 5 seconds to turn ON the
Slave.