Overview Scope; Unit Features - Pilz PNOZ ma1p Operating Manual

Configurable safety systems pnozmulti
Hide thumbs Also See for PNOZ ma1p:
Table of Contents

Advertisement

Overview
2
Overview
2.1
Scope
Expansion module PNOZ ma1p
}
Jumper
}
2.2

Unit features

Using the product PNOZ ma1p:
Expansion module for connection to a base unit from the configurable control system
PNOZmulti
The product has the following features:
2 safe analogue inputs for current or voltage measurement
}
Each input can be configured separately
}
Voltage range: -10,24 ... +10.2375 V
}
Current range: 0 ... 25.59 mA
}
Resolution
}
Range monitoring to monitor for wiring errors or errors in the sensor (4 range limits can
}
be configured)
Threshold value monitoring to monitor process variables (8 threshold values can be
}
configured)
Max. 4 PNOZ ma1p units can be connected to the base unit
}
Exact analogue value can be passed to a fieldbus for diagnostic purposes
}
LEDs for
}
Coated version:
}
Increased environmental requirements (see
Plug-in connection terminals:
}
either spring-loaded terminal or screw terminal available as an accessory (see order
reference)
Please refer to the document "PNOZmulti System Expansion" for the PNOZmulti base
}
units that can be connected.
Operating Manual PNOZ ma1p
21687-EN-04
Voltage measurement: 13 Bit (signed 12 Bit)
Current measurement: 12 Bit
Operating state
State of the input signals (Ch0, Ch1)
Error
Technical details [
19])
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

773812773813