Safety Characteristic Data - Pilz PNOZ ma1p Operating Manual

Configurable safety systems pnozmulti
Hide thumbs Also See for PNOZ ma1p:
Table of Contents

Advertisement

Technical details
8.1

Safety characteristic data

Operating
EN ISO
mode
13849-1:
2008
PL
1-channel
PL e
PL e
2-channel
All the units used within a safety function must be considered when calculating the safety
characteristic data.
Operating Manual PNOZ ma1p
21687-EN-04
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
EN ISO
EN 62061
13849-1:
SIL CL
2008
Category
Cat. 4
SIL CL 3
Cat. 4
SIL CL 3
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
EN 62061
IEC 61511
PFH
[1/h]
SIL
D
8,71E-09
SIL 3
8,71E-09
SIL 3
IEC 61511
EN ISO
13849-1:
PFD
2008
T
[year]
M
4,21E-05
20
4,21E-05
20
22