I/O DATA DESCRIPTIONS
■ MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
Shows each module's availability and error status.
15
■ ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). Negative percentage is represented in
2's complements.
15
■ TEMPERATURE DATA (models: R3-RS4, TS4 and US4)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2's complements.
15
■ 16-POINT DISCRETE DATA (models: R3-DA16 and DC16)
15
0 : OFF (open)
1 : ON (close)
0
Module 1
Module 2
Module 3
:
Module 16
0
0
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
:
Input 16 (Output 16)
R3-NC2
EM-842 Rev.8