Operating instructions Non-Contact Safety System CES-AZ-UES-… Contents About this document ..................... 4 1.1. Scope ............................4 1.2. Target group ..........................4 1.3. Key to symbols ..........................4 1.4. Supplementary documents ......................4 Correct use ......................5 Description of the safety function ................7 Exclusion of liability and warranty ................. 8 General safety precautions ...................
Important! Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc. no. in the search box. (Translation of the original operating instructions) 2105274-12-08/20...
2. Correct use Evaluation units of the series CES-AZ are used to evaluate safety-related signals from EUCHNER read heads. Depending on the read heads used, the system can form an interlocking device with or without guard locking. The system meets the requirements according to EN IEC 60947-5-3.
Page 6
Operating instructions Non-Contact Safety System CES-AZ-UES-… Important! Ì The user is responsible for the proper integration of the device into a safe overall system. For this purpose, the overall system must be validated, e.g. in accordance with EN ISO 13849-2. Ì Correct use requires observing the permissible operating parameters (see technical data). Ì...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 3. Description of the safety function Devices from this series feature the following safety functions: The following applies in combination with read heads without guard locking (CES read heads) and read heads with guard locking for process protection (CEM read heads): Monitoring of the position of a guard (interlocking device according to EN ISO 14119)
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. For this reason you should archive a printed copy of the operating instructions. You can download the operating instructions from www.euchner.com. (Translation of the original operating instructions) 2105274-12-08/20...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 6. Function The safety system consists of three components: Ì Coded actuator Ì Read head Ì Evaluation unit The number of read heads that can be connected depends on the evaluation unit: Ì CES-AZ-UES-01B: 1 read head ...
Jumper for teach-in operation H11/H12 Read head 1 connection Read head 1 shield Test input (see 9.3.1. Self‑test CES-AZ-UES-01B with test input TST on page EUCHNER 105139 Semiconductor monitoring output Diagnostic output 13, 14 Connection for relay contact A, safety relay enable...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 7. Mounting NOTICE Device damage due to improper installation or unsuitable ambient conditions. Ì Read heads and actuators must not be used as a mechanical end stop. Ì Observe EN ISO 14119:2013, sections 5.2 and 5.3, for information about fastening the safety switch and the actuator.
The tightening torque for the screws on the connection terminals must be 0.6 … 0.8 Nm. Ì The connection cable for the read heads must only be extended using EUCHNER plug connectors, and adequate consideration must be given to EMC. Intermediate terminals must not be used.
Non-Contact Safety System CES-AZ-UES-… 8.4. Connection example for CES-AZ-UES-01B 24 VDC Trans- ponder Read- head CES-AZ-UES-01B EUCHNER Start 105139 23 24 13 14 feedback loop Important! To achieve category 4 according to EN ISO 13849-1, it is necessary to monitor the downstream contactors (here: contacts on -K3 and -K4 in the feedback loop).
Read- Read- head head J1 J2 SH1 CES-AZ-UES-02B EUCHNER Start 105140 23 24 13 14 feedback loop Important! To achieve category 4 according to EN ISO 13849-1, it is necessary to monitor the downstream contactors (here: contacts on -K3 and -K4 in the feedback loop).
J1 J2 SH1 CES-AZ-UES-04B EUCHNER Start 105141 feedback loop Important! To achieve category 4 according to EN ISO 13849-1, it is necessary to monitor the downstream contactors (here: contacts on -K3 and -K4 in the feedback loop).
Operating instructions Non-Contact Safety System CES-AZ-UES-… 9. Setup 9.1. LED indicators Meaning Designation Color STATE green Status indication (multifunction display using flashing modes) yellow Safety circuit closed Ì Operating fault or Ì External fault (fault in the feedback loop) or Ì...
Operating instructions Non-Contact Safety System CES-AZ-UES-… - Parameter setting operation starts (STATE LED flashes at approx. 1 Hz) - Wait for acknowledgment of the parameter setting operation (STATE LED goes out after approx. 10 seconds) 5. End parameter setting operation - Remove jumper between J1 and J2 (for CES-AZ-UES-01B between J and 0V) - For operating mode Manual start: start button must be connected - For operating mode with feedback loop: feedback loop must be connected - Press reset button or interrupt operating voltage for at least 10 seconds...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 9.3. Functional check After installation and any fault, the safety function must be fully checked. Proceed as follows: WARNING Danger of fatal injury as a result of faults in installation and functional check. Ì Before carrying out the functional check, make sure that there are no persons in the danger zone.
Operating instructions Non-Contact Safety System CES-AZ-UES-… 10. System status table LED indicator Operating mode State 4 Hz Initial setup after delivery without jumper connected to J1, J2 or J, 0V. Setup 1 Hz Parameter setting operation Acknowledgment of completion of parameter setting operation. 15 Hz Self-test, duration approx.
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11. Technical data 11.1. Evaluation unit CES-AZ-UES-01B Approvals Ì Housing for rail mounting, IP20 Ì Relay output Ì 1 read head can be connected Dimension drawing 22,5 Safety Unit STATE OUT RESET CES-AZ Multicode Suitable for standard 35 mm mounting rail Switching characteristics Ì...
Page 21
Operating instructions Non-Contact Safety System CES-AZ-UES-… Technical data for CES-AZ-UES-01B Value Parameter Unit min. typ. max. Housing material PA6.6 plastic Dimensions 114 x 99 x 22.5 Weight Ambient temperature at U = DC 24 V °C Atmospheric humidity, not condensing Degree of protection IP20 Degree of contamination Mounting Mounting rail 35 mm according to EN 60715 TH35 Number of read heads...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.2. Evaluation unit CES-AZ-UES-02B Approvals Ì Housing for rail mounting, IP20 Ì Relay output Ì 2 read heads can be connected Dimension drawing STATE OUT DIA Safety Unit RESET CES - AZ Multicode Suitable for 35 mm mounting rail according to EN 60715 Switching characteristics Ì...
Page 23
Operating instructions Non-Contact Safety System CES-AZ-UES-… Technical data for CES-AZ-UES-02B Value Parameter Unit min. typ. max. Housing material PA6.6 plastic Dimensions 114 x 99 x 45 Weight 0.25 Ambient temperature at U = DC 24 V °C Atmospheric humidity, not condensing Degree of protection IP20 Degree of contamination Mounting Mounting rail 35 mm according to EN 60715 TH35...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.3. Evaluation unit CES-AZ-UES-04B Approvals Ì Housing for rail mounting, IP20 Ì Relay output Ì 4 read heads can be connected Dimension drawing STATE OUT DIA Safety Unit RESET CES - AZ Multicode Suitable for 35 mm mounting rail according to EN 60715 Switching characteristics Ì...
Page 25
Operating instructions Non-Contact Safety System CES-AZ-UES-… Technical data for CES-AZ-UES-04B Value Parameter Unit min. typ. max. Housing material PA6.6 plastic Dimensions 114 x 99 x 45 Weight 0.25 Ambient temperature at U = DC 24 V °C Atmospheric humidity, not condensing Degree of protection IP20 Degree of contamination Mounting Mounting rail 35 mm according to EN 60715 TH35...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.4. Read head CES-A-LNN-… Approvals Ì Cube-shaped design 42 x 25 mm Ì Attachment compatible with series CES-A-LNA/LCA Ì LED for the indication of the door position Dimension drawing With connecting cable Active face Active face Active face With M8 plug connector Typical actuating range...
Page 27
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with connection cable Shield Read head H11 H12 Evaluation unit CES-AZ-ALS-… Technical data Parameter Value Unit min. typ. max. Housing material Reinforced thermoplastic (PBT), fully encapsulated Dimensions 42 x 25 x 12 Weight (without connection cable) 0.025 Ambient temperature °C...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.5. Read head CES-A-LSP-… Approvals Ì Optimized for aluminum profile mounting Ì LED for the indication of the door position Dimension drawing Mounting distance CES-A-LSP-… ≤10 With With 18,1 M5 plug connector connecting cable Ø...
Page 29
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with connection cable Shield Read head CES-A-LSP H11 H12 Evaluation unit CES-AZ-UES-… Technical data Parameter Value Unit min. typ. max. Housing material PA6 GF30 Weight (without connection cable) 0.02 Ambient temperature °C Degree of protection IP67...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.6. Read head CES-A-LNA-… Approvals Ì Cube-shaped design 42 x 25 mm Ì Hard-wired cable Dimension drawing "l" CES-A-L XXXXXX 2 M4 x 14 safety screws included 32 ±0,1 Active face Active face Typical actuating range With evaluation unit CES-AZ-UES-… and actuator CES-A-BBA NOTICE For a side approach direction for the actuator and read head, a minimum distance of s = 3 mm must be maintained so that the actuating range of the side lobes is not entered.
Page 31
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with connection cable Shield Read head H11 H12 SH1 Evaluation unit CES-AZ-UES-… Technical data Parameter Value Unit min. typ. max. Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 42 x 25 x 12 Weight (incl. 10 m cable) Ambient temperature °C Degree of protection...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.7. Read head CES-A-LNA-SC Approvals Ì Cube-shaped design 42 x 25 mm Ì M8 plug connector Dimension drawing 32,6 32 ±0,1 CES-A-L 077715 Active face min.38 Active face 2 M4 x 14 safety screws included Cable outlet with angled connector CES-A-L 077715 Typical actuating range With evaluation unit CES-AZ-UES-…...
Page 33
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with plug connector Shield H11 H12 SH1 View on the plug connector of the Evaluation unit read head CES-AZ-UES-… Technical data Parameter Value Unit min. typ. max. Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 42 x 25 x 12 Weight (incl.
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.8. Read head CES-A-LCA-… Approvals Ì Cube-shaped design 42 x 25 mm Ì PE-HD plastic housing material, suitable for use in aggressive media (e.g. acids, alkalis) Dimension drawing ± 0,1 Active face Flat seal Active face 2 M4 x 14 safety screws included NOTICE The flat seal provided must be used during assembly.
Page 35
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with connection cable Shield Read head H11 H12 SH1 View on the plug connector of the Evaluation unit read head CES-AZ-UES-… Technical data Parameter Value Unit min. typ. max. Housing material PE-HD plastic without reinforcement, fully encapsulated Flat seal material Fluororubber 75 FPM 4100...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.9. Read head CES-A-LQA-SC Approvals Ì Cube-shaped design 50 x 50 mm Ì M8 plug connector Dimension drawing 20,2 0,25 ±0,15 Active face Typical actuating range - 3 0 - 3 0 With actuator CES-A-BBA or CES-A-BCA With actuator CES-A-BQA on evaluation unit CES-AZ-…-01B (Translation of the original operating instructions) 2105274-12-08/20...
Page 37
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with connection cable Shield Read head H11 H12 Evaluation unit CES-AZ-UES-… Technical data Parameter Value Unit min. typ. max. Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 50 x 50 x 20.2 Weight 0.08 Ambient temperature °C Degree of protection...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.10. Read head CES-A-LMN-SC Approvals Ì Cylindrical design M12 Ì M8 plug connector Dimension drawing Reading distance connected Active face 1) Clear zone (area of the active face without metal housing) NOTICE The read head is allowed to be installed as a maximum up to the clear zone (area of the active face without metal housing).
Page 39
Operating instructions Non-Contact Safety System CES-AZ-UES-… Terminal assignment Read head with plug connector Shield H11 H12 SH1 View on the plug connector of the Evaluation unit read head CES-AZ-UES-… Technical data Parameter Value Unit min. typ. max. Housing material Nickel-plated CuZn housing sleeve Plastic PBT GF20 cap Dimensions M12 x 1, length 38...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.11. Actuator CES-A-BBN Ì Cube-shaped design 42 x 25 mm Ì Attachment compatible with series CES-A-LNA/LCA Dimension drawing for CES-A-BBN Active face Active face Technical data Value Parameter Unit min. typ. max. Housing material Reinforced thermoplastic (PBT), fully encapsulated Dimensions 42 x 45 x 12 Weight...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.12. Actuator CES-A-BSP Ì Optimized for aluminum profile mounting Dimension drawing for CES-A-BSP 18,1 Ø 5,2 Active face Technical data Value Parameter Unit min. typ. max. Housing material PA6 GF30 Weight 0.02 Ambient temperature °C Degree of protection IP67...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.13. Actuator CES-A-BDN-06 Ì Cylindrical design ∅ 6 mm Dimension drawing for CES-A-BDN-06 Installation options +0,1 +0,5 30 * 30 * * Metal-free zone Technical data Value Parameter Unit min. typ. max. Housing material Macromelt PA-based plastic Dimensions 26 x ∅...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.14. Actuator CES-A-BBA/CES-A-BCA Ì Cube-shaped design 42 x 25 mm Ì CES-A-BCA suitable for use in aggressive media (e.g. acids, alkalis) Ì In combination with read head CES-A-LNA…/CES-A-LCA… Dimension drawing for CES-A-BBA CES-A-B 071840 32 ±0,1 Active face Active face 2 M4 x 14 safety screws included Dimension drawing for CES-A-BCA...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.15. Actuator CES-A-BQA Ì Cube-shaped design 50 x 50 mm Dimension drawing for CES-A-BQA 20,2 0,25 ±0,15 Active face Technical data Value Parameter Unit min. typ. max. Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 50 x 50 x 20.2 Weight 0.07 Ambient temperature °C...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.16. Actuator CES-A-BDA-20 Ì Round design ∅ 20 mm Ì In combination with read head CES-A-LNA…/CES-A-LCA… Dimension drawing Active face Active face ∅ 20 Technical data Value Parameter Unit min. typ. max. Housing material PC plastic Dimensions ∅...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.17. Actuator CES-A-BDA-18 Ì Round design ∅ 18 mm Ì In combination with read head CES-A-LNA…/CES-A-LCA… Dimension drawing ∅7 ∅4,4 Active face Active face ∅18 Technical data Value Parameter Unit min. typ. max. Housing material - Sleeve PBT-GF30, thermoplastic plastic - Active face...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 11.18. Actuator CES-A-BMB Ì Cylindrical design M12 x 75 Ì In combination with read head CES-A-LMN-SC (actuating range on request for read head CES-A-LNA…/LCA…) Dimension drawing 0,80 Active face NOTICE Ì The actuator can be screwed into the M12 x 0.75 thread provided with the aid of an insertion tool (order no.
12. Ordering information and accessories Tip! Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed in “Accessories.”...
Operating instructions Non-Contact Safety System CES-AZ-UES-… 15. Declaration of conformity 2105274-12-08/20 (Translation of the original operating instructions)
Page 50
Operating instructions Non-Contact Safety System CES-AZ-UES-… (Translation of the original operating instructions) 2105274-12-08/20...
Page 51
Operating instructions Non-Contact Safety System CES-AZ-UES-… 2105274-12-08/20 (Translation of the original operating instructions)