Exception Codes

å Exception Code Tables
When the adjustable frequency drive responds to
the master via the Modbus serial network, it uses
the function code field to indicate either a normal
(error-free) response or an error (called an exception
response). In an error-free response, the drive simply
echoes the original function code. For an exception
Modbus
Code
(decimal)
00
The parameter number does not exist
01
There is no write access to the parameter
02
The data value exceeds the parameter limits
03
The used sub-index does not exist
04
The parameter is not of the array type
05
The data type does not match the parameter called
06
Only Reset
07
Not changeable
11
No write access
17
Data change in the parameter called is not possible in the present mode of the drive. Some
parameters can only be changed when the motor has stopped.
18
Other error
130
There is no bus access to the parameter called
131
Data Change is not possible because factory setup is selected
Modbus RTU Errors
Modbus
Code
(decimal)
64
Invalid Data Address
65
Invalid Message Length
66
Invalid Data Length or Value
67
Invalid Function Code
MG.10.S1.22 - VLT is a registered Danfoss trademark
VLT® Serie 2800 and VLT® Serie 6000 Modbus RTU
Errors
Meaning
response, the drive will return a code that is equivalent
to the original function code with its most-significant bit
set to a logic 1. In addition, the drive places a unique
code into the data field of the response message. This
tells the master what kind of error occurred, or the
reason for the exception. The tables below identify
the codes and describe their meaning.