Indoor/Outdoor Unit Installation Drawings - Daikin R32 Split Series Installation Manual

Hide thumbs Also See for R32 Split Series:
Table of Contents

Advertisement

Indoor/outdoor unit
installation drawings
For installation of the indoor units, refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)
CAUTION
• Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the
indoor unit in order to add another indoor unit later.
Make sure no dirt or moisture gets into either side of the embedded branch piping.
See "6. Refrigerant piping work" on page 11 for details.
• It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
NOTE:
The DHW generator for Multi or the Hybrid for Multi are considered as one room connection.
For the correct combination see the combination table and the installation manual of the DHW generator for Multi or the Hybrid
for Multi.
Max. allowable refrigerant charge amount
3MXM40*
2.2kg
3(A)MXM52*
2.2kg
3MXM68*
2.4kg
4MXM68*
2.6kg
4MXM80*
3.2kg
5MXM90*
3.3kg
Refrigerant piping must be kept to
a minimum.
Minimum floor area for installation
3MXM40*
4.7m
2
3(A)MXM52*
4.7m
2
3MXM68*
5.5m
2
4MXM68*
6.5m
2
4MXM80*
9.8m
2
5MXM90*
10.4m
2
If there is the danger of the unit falling
or overturning, fix the unit with
foundation bolts, or with wire or other
means.
If the location does not have good
drainage, place the unit on a level
mounting base (or a plastic pedestal).
Install the outdoor unit in a level
position. Failure to do so may result in
water leakage or accumulation.
English
Caulk
pipe hole
gap
with putty.
Allow 300mm of
work space below
the ceiling surface.
Also insulate the connection on the outdoor unit.
Level mounting
base (optional parts)
Use tape or insulating material on all connections
to prevent air from getting in between the copper
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed
above.
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe's cut line.
Wrap the insulation
pipe with the finishing
tape from bottom to top.
Refrigerant piping must
be protected from
physical damage.
Install a plastic cover or
equivalent.
Allow space for piping
and electrical servicing.
Stop valve cover
unit: mm
Clamping material
Insulation tube
Tape
Service cover
4