Final Checks (With Burner Operating) - Riello RLS 70 Installation, Use And Maintenance Instructions

Dual fuel light oil/ gas burners. two stage operation
Table of Contents

Advertisement

6.11

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the knob of the gas maximum pressure switch to the
minimum end of scale position
 Turn the air pressure switch knob to the maximum end of
scale position
 Turn off the burner and cut off the power
 Disconnect the minimum gas pressure switch connector
 Disconnect the UV probe wire
Make sure that the mechanical locking systems
on the various adjustment devices are fully
tightened.
ATTENTION
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to
ignition failure
35
GB
Tab. M
20139915