Gas Train; Gas Train Installation; Gas Pressure - Riello RLS 70 Installation, Use And Maintenance Instructions

Dual fuel light oil/ gas burners. two stage operation
Table of Contents

Advertisement

5.12.2 Gas train

Type-approved in accordance with EN 676 and supplied
separately from the burner.
To select the correct gas train model, refer to the manual "Burner-
gas train combination" supplied with the unit.

5.12.3 Gas train installation

Disconnect the electrical power using the main
switch.
DANGER
Check that there are no gas leaks.
Pay attention when handling the train: danger of
crushing of limbs.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
The operator must use the required equipment
during installation.
The gas train must be connected to the gas connection 1)
(Fig. 27), using the flange 2), the gasket 3) and the screws 4)
supplied with the burner.
The train can enter the burner from the right or left side,
depending on which is the most convenient, see Fig. 27.
Installation
D722
Fig. 27
25

5.12.4 Gas pressure

Tab. K indicates the pressure drops of the combustion head and
gas butterfly valve, on the basis of the burner operating output.
Model
kW
465
515
565
615
665
715
765
814
698
760
825
890
955
1020
1085
1163
930
1010
1090
1170
1250
1395
Data of head thermal power and gas pressure
refer to operation with gas butterfly valve fully
open (90°).
ATTENTION
The values shown in Tab. K refer to:
Natural gas G 20 NCV 9.45 kWh/Sm
Natural gas G 31 NCV 27 kWh/Sm
Column 1
Combustion head pressure drop.
Gas pressure measured at test point 1)(Fig. 28), with:
combustion chamber at 0 mbar;
Burner operating in 2nd stage
Gas G20 (methane) - G31 (propane)
To calculate the approximate output at which the burner operates
in the 2nd stage:
subtract the combustion chamber pressure from the gas
pressure measured at test point 1) (Fig. 28).
Find in Tab. K related to the burner concerned, the pressure
value closest to the result of the subtraction.
Read the corresponding output on the left.
GB
1 p (mbar)
G20
G25
5.5
8.2
5.6
8.3
5.7
8.5
5.8
8.6
5.9
8.8
6.0
8.9
6.1
9.1
6.2
9.2
8.0
11.9
8.3
12.4
8.6
12.8
8.9
13.3
9.2
13.7
9.4
14.0
9.7
14.5
10.0
14.9
9.3
13.9
9.5
14.2
9.7
14.5
9.9
14.8
10.4
15.5
11.5
17.1
3
(8.2 Mcal/Sm
3
(23.2 Mcal/Sm
G31
6.3
6.4
6.5
6.7
6.8
7.1
7.4
7.8
10.3
10.5
10.8
11.1
11.4
11.6
11.8
12.0
10.5
10.9
11.4
11.8
12.9
14.4
Tab. K
3
)
3
)
20139915

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents