Faults - Possible causes - Solutions

The LFL1.333... control box is equipped with a lockout indicator
(Fig. 46) that turns during the start-up programme, and is visible
from the small lockout window.
When the burner does not start or stops, due to a failure, the
symbol that appears on the indicator indicates the type of
interruption.
The positions of the lockout indicator are shown in Fig. 47.
S8888
Fuse replacement
The fuse 2)(Fig. 48) is in the rear part of the control box. A spare
fuse 1) is also available: it can be extracted after breaking the
panel tab A) that houses it. In the event that fuse 2) has been
tripped, replace it as shown in Fig. 48.
Find a list of faults, causes and possible solutions for a set of
failures that may occur and result in irregular burner operation or
no functioning at all.
If a burner malfunction is detected, first of all:
check that the electrical wiring is adequately connected;
check whether fuel is delivered;
check that every adjustment parameter is adequately set.
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
locks out for a third time, contact the customer
ATTENTION
service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
T6,3H
250V
1
A
20139915
Faults - Possible causes - Solutions
P
2
S8884
Fig. 48
40
S8889
1
2
GB
Lockout indicator
a-b
Start-up sequence
b(b')
Idle
stages
(without
contact confirmation)
b(b')-a
Post-purging
programme
Fig. 46