Electrical Connections; Supply Cables And External Connections Passage - Riello RLS 70 Installation, Use And Maintenance Instructions

Dual fuel light oil/ gas burners. two stage operation
Table of Contents

Advertisement

5.13

Electrical connections

Notes on safety for the electrical wiring
 The electrical wiring must be carried out with the electrical supply disconnected.
 Electrical wiring must be made in accordance with the regulations currently in force in the country of destination
and by qualified personnel. Refer to the wiring diagrams.
 The manufacturer declines all responsibility for modifications or connections different from those shown in the
DANGER
wiring diagrams.
 Check that the electrical supply of the burner corresponds to that shown on the identification label and in this
manual.
 The burner has been type-approved for intermittent use.
This means they should compulsorily be stopped at least once every 24 hours to enable the control box to
perform checks of its own start-up efficiency. Normally, burner stopping is guaranteed by the boiler's thermostat/
pressure switch.
 If this is not the case, a time switch should be fitted in series to TL to stop the burner at least once every 24 hours.
Refer to the wiring diagrams.
 The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing system,
made according to current standards. It is necessary to check this fundamental safety requirement. In the event of
doubt, have the electrical system checked by qualified personnel. Do not use the gas tubes as an earthing system
for electrical devices.
 The electrical system must be suitable for the maximum power absorption of the device, as indicated on the label
and in the manual, checking in particular that the section of the cables is suitable for that level of power
absorption.
 For the main power supply of the device from the electricity mains:
- do not use adapters, multiple sockets or extensions;
- use a multiple pole switch with at least a 3 mm gap between the contacts (overvoltage category III), as
envisaged by the present safety standards.
 Do not touch the device with wet or damp body parts and/or in bare feet.
 Do not pull the electric cables.
Before carrying out any maintenance, cleaning or checking
operations:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel shut-off valve.
DANGER
Avoid condensate, ice and water leaks from
forming.
DANGER
If the cover is still present, remove it and proceed with the
electrical wiring according to the wiring diagrams.
Use flexible cables according to standard EN 60 335-1.
5.13.1 Supply cables and external connections
passage
All the cables to be connected to the burner terminal board
8)(Fig. 29) must be threaded through cable grommets.
The use of the cable grommets and the pre-blanked holes can be
done in different manners; for example (Fig. 29):
Installation
Key (Fig. 29)
1
Pg 13.5
2
Pg 11
3
Pg 11
4
Pg 9
5
Pg 13.5
6
Pg 13.5
7
Pg 11
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
27
GB
Three-phase power supply
Single-phase power supply
TL remote control
TR remote control
Gas valves
Gas pressure switch or device
for leak detection control
Bore, if you want to add
a cable entry
D1174
Fig. 29
20139915

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents