2-10. E: 58. Intake grille error (Indoor unit)

Indicator
Indoor unit
Indoor unit main PCB
Detective actuator
Micro switch
Forecast of cause
Check point 1. Check limit switch
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
-> If micro switch is detective, replace it.
Check point 2. Check Connector (CN11)/wire
Check loose contact of CN11/shorted wire (pinched wire).
-> Replace micro switch if the wire is abnormal
Check point 3. Replace main PCB
If Check Point 1 and 2 do not improve the symptom, change main PCB.
2-10. E: 58. Intake grille error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
When the Micro switch is detected open while running
the compressor.
End
- (03-20) -
5 time flash
8 time flash
Continuous flash
E: 58
Micro switch failure
Shorted connector/wire
Main PCB failure
2. Troubleshooting with error code