Check point 3. Check the solenoid coil and 4-way valve
Solenoid coil
Remove CN30 from PCB and check the resistance value of coil. Resistance value is 1.88 kΩ —
2.29 kΩ (at 68 °F (20 °C)).
→ If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Check the voltage of 4-way valve
Check the voltage CN30 of Main PCB.
→ Check if AC 187 V (AC 208 V -10%) to AC 253 V (AC 230 V +10%) appears at CN30 of Main
PCB.
Heating operation
→ If it is not voltage, Replace Main PCB.
Cooling operation
→ If it is voltage, Replace Main PCB.
Check point 5. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
2-21. E: 99. 4-way valve error (Outdoor unit)
End