Fujitsu AOUG09LZAH1 Design & Technical Manual

Hide thumbs Also See for AOUG09LZAH1:
Table of Contents

Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ASUG09LZAS
ASUG12LZAS
ASUG15LZAS
AOUG09LZAH1
AOUG12LZAH1
AOUG15LZAH1
For Extra Cold Climate Area
DR_AS117EF_03
2022.10.12

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AOUG09LZAH1

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASUG09LZAS ASUG12LZAS ASUG15LZAS OUTDOOR AOUG09LZAH1 AOUG12LZAH1 AOUG15LZAH1 DR_AS117EF_03 2022.10.12...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google LLC. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Wireless LAN control ..................4 2-1. System requirement......................4 2-2. Wireless LAN function list ....................5 3. Dimensions....................6 3-1. Models: ASUG09LZAS, ASUG12LZAS, and ASUG15LZAS ...........6 4. Wiring diagrams ....................8 4-1. Models: ASUG09LZAS, ASUG12LZAS, and ASUG15LZAS ...........8 5.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............53 1. Specifications....................54 2. Dimensions....................55 2-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 .........55 3. Installation space ..................56 3-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 .........56 4. Refrigerant circuit ..................59 4-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 .........59 5. Wiring diagrams ..................60 5-1.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASUG09LZAS ASUG12LZAS ASUG15LZAS...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter heat pump Model name ASUG09LZAS ASUG12LZAS ASUG15LZAS Power supply 208/230 V ~60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V 2.64 3.52 4.25 Rated Btu/h 9,000 12,000 14,500 Cooling 0.91—3.52 0.91—3.99 0.91—5.39 Min.—Max.
  • Page 7 Wall mounted Type Inverter heat pump Model name ASUG09LZAS ASUG12LZAS ASUG15LZAS °F (°C) 64 to 90 (18 to 32) Cooling Operation range 80 or less Heating °F (°C) 60 to 86 (16 to 30) ™ Remote controller type Wireless (Wired, Mobile app* [FGLair ] [option]) NOTES:...
  • Page 8: Wireless Lan Control

    After installation of Mobile App, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the Wireless LAN (WLAN) control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 4 - 2-1. System requirement...
  • Page 9: Wireless Lan Function List

    2-2. Wireless LAN function list NOTE: To use Wireless LAN control, user registration in advance and access to the wireless home network are required. Attached wireless Item Mobile App remote controller Operation on/off ○ ○ Operation mode setting ○ ○ Set temperature setting ○...
  • Page 10: Dimensions

    3. Dimensions 3-1. Models: ASUG09LZAS, ASUG12LZAS, and ASUG15LZAS Unit: in (mm) 38-9/16 (980) 9-7/16 (240) 3-1/16 16-1/4 (413) 15-3/4 (400) 3-9/16 (77) (90) Outline of indoor unit for pipe inlet for pipe inlet Ø 2-9/16 (65) Ø 2-9/16 (65) 4-1/2 (115) 2-13/16 (72) 2-3/8 16-7/8 (429)
  • Page 11 ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: in (mm) 2 (40) or more Wall hook bracket 3 (70) or more Outline of the indoor unit 7 (160) or more 5 (117) or more 60 (1,500) or more - 7 - 3-1.
  • Page 12: Wiring Diagrams

    4. Wiring diagrams 4-1. Models: ASUG09LZAS, ASUG12LZAS, and ASUG15LZAS - 8 - 4-1. Models: ASUG09LZAS, ASUG12LZAS, and ASUG15LZAS 4. Wiring diagrams...
  • Page 13: Capacity Table

    5. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 5-1.
  • Page 14 ¢ Model: ASUG12LZAS Indoor temperature °FDB °FWB °FDB kBtu kBtu kBtu kBtu kBtu kBtu 10.34 9.52 0.28 11.53 9.58 0.28 12.72 10.47 0.29 13.11 11.30 0.29 13.87 11.21 0.29 14.67 11.96 0.30 10.26 9.44 0.33 11.44 9.47 0.33 12.62 10.34 0.35 13.01 11.19...
  • Page 15: Heating Capacity

    5-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: ASUG09LZAS Indoor temperature °FDB °FDB °FWB kBtu kBtu kBtu kBtu 11.6 2.15 11.4 2.19 11.1 2.23 10.5 2.31 14.7 2.16 14.3 2.20 14.0 2.24 13.3...
  • Page 16 ¢ Model: ASUG15LZAS Indoor temperature °FDB °FDB °FWB kBtu/h kBtu/h kBtu/h kBtu/h 17.1 2.77 16.7 2.82 16.3 2.88 15.5 2.98 19.6 2.78 19.1 2.84 18.6 2.89 17.7 3.00 22.0 2.79 21.5 2.85 21.0 2.90 19.9 3.01 22.7 2.68 22.2 2.73 21.6 2.78 20.5...
  • Page 17: Fan Performance

    6. Fan performance 6-1. Air velocity distributions ¢ Models: ASUG09LZAS and ASUG12LZAS Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) Top view 2 (0.5) 3 (1.0) 7 (2.0) Horizontal louver: Up Vertical louver: Center (ft) Unit: ft/s (m/s) (ft) 7 (2.0) 2 (0.5)
  • Page 18 ¢ Model: ASUG15LZAS Fan speed Operation mode Measuring conditions HIGH (ft) Unit: ft/s (m/s) Top view 7 (2.0) 3 (1.0) 2 (0.5) Horizontal louver: Up Vertical louver: Center (ft) Unit: ft/s (m/s) (ft) 7 (2.0) 2 (0.5) 3 (1.0) Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 19: Airflow

    6-2. Airflow ¢ Model: ASUG09LZAS  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 15 - 6-2. Airflow 6. Fan performance...
  • Page 20 ¢ Model: ASUG12LZAS  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 16 - 6-2. Airflow 6. Fan performance...
  • Page 21 ¢ Model: ASUG15LZAS  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow 1,020 HIGH QUIET - 17 - 6-2. Airflow 6. Fan performance...
  • Page 22: Operation Noise (Sound Pressure)

    7. Operation noise (sound pressure) 7-1. Noise level curve ¢ Models: ASUG09LZAS and ASUG12LZAS  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15...
  • Page 23: Sound Level Check Point

    7-2. Sound level check point Microphone Microphone 40 in (1 m) NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 19 - 7-2. Sound level check point 7. Operation noise (sound pressure)
  • Page 24: Safety Devices

    8. Safety devices Model Type of Protection form protection ASUG09LZAS ASUG12LZAS ASUG15LZAS Circuit Current fuse (PCB*) 250 V, 3.15 A protection 257±18 °F (125±10 °C) Activate Thermal Fan motor stop Fan motor protector protection 212±18 °F (100±10 °C) program Reset Fan motor restart *PCB: Printed Circuit Board - 20 -...
  • Page 25: External Input And Output

    9. External input and output External input and output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB External input External output Connector Input select Input signal Operation/Stop CN313/ Edge/Pulse Dry contact/ CN314 Forced stop —...
  • Page 26: External Input

    9-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m). •...
  • Page 27: External Output

    9-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ External Input and Output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). •...
  • Page 28: Combination Of External Input And Output

    9-3. Combination of external input and output By combining the function setting of the rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External Input and Output PCB...
  • Page 29: Details Of Function

    9-4. Details of function ¢ Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation External Input and 46-00...
  • Page 30 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Forced stop External Input and 46-02 CN313 Output PCB On →...
  • Page 31 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation Stop External Input and 46-03 CN313 (Remote Output PCB On →...
  • Page 32 • Forced thermostat off function Rotary SW on External External input Input signal Command Input and Output PCB Off → On Thermostat off External Input and Output PCB CN313 On → Off Normal operation Input Compressor Room temp. Set temp. - 28 - 9-4.
  • Page 33 ¢ Control output function • Operation/Stop status Rotary SW on External Output External output Command Input and Output PCB signal Off → On Operation External Input and Output PCB CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 34 • External heater output Rotary SW on External Output External output Command Input and Output PCB signal Off → On Heater on External Input and Output PCB CN312 On → Off Heater off - 30 - 9-4. Details of function 9.
  • Page 35 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 31 - 9-4.
  • Page 36  Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 37  Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 38  Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. When out- door temperature is high, the heating is performed by using heat pump only. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature.
  • Page 39 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Heat pump Combination zone prohibition only zone Outdoor temperature zone * zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 40  Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
  • Page 41 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Combination zone Outdoor temperature zone * prohibition zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 42: Remote Controller

    10. Remote controller 10-1. Wireless remote controller ¢ Overview Signal SENSOR button transmitter MODE button FAN button MIN. HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button...
  • Page 43 ¢ Specifications  Controller Unit: in (mm) Top view 11/16 2-3/8 (17) (61) Front view Side view Size (H × W × D) in (mm) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) Weight oz (g) 4.4 (124) (without batteries) ...
  • Page 44: Function Settings

    11. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 45 NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. - 41 - 11-1.
  • Page 46 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Remote controller address setting Filter sign...
  • Page 47 2) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 48 4) Room temperature control for wired remote controller sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”.
  • Page 49 7) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 50 11) Control switching of external heaters Sets the control method for external heater to be used. For details, refer to “External heater output” in Chapter 9-4. "Details of function" on page 25. Function Factory Setting value Setting description number setting Auxiliary heater control 1 ♦...
  • Page 51 14) Outdoor temperature zone boundary temperature B Setting required if changing of the outdoor temperature setting for heat pump only zone is required when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details, refer to “External heater output” in Chapter 9-4. "Details of function"...
  • Page 52: 11-2.Custom Code Setting For Wireless Remote Controller

    11-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 53: 11-3.Switching The Temperature Unit Of Remote Controller

    11-3. Switching the temperature unit of remote controller Displayed temperature unit on the remote controller LCD can be switched between °F (Fahrenheit) and °C (Celsius). To change temperature unit, do as follows: Press the TEMP. (Up) button ( ) for at least 5 seconds to display the current temperature unit. (Factory setting: °F) Press the TEMP.
  • Page 54: Accessories

    12. Accessories Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Tapping screw (large) Installation manual Tapping screw (small) Remote controller Battery Remote controller Filter holder holder Cloth tape Air cleaning filters Wall hook bracket - 50 - 12. Accessories...
  • Page 55: Optional Parts

    13. Optional parts 13-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wire type: Non-polar 2-wire Optional communication kit is necessary for installation. NOTE: When this remote controller is connected, wireless remote controller cannot be Office...
  • Page 56: 13-2.Others

    13-2. Others Exterior Part name Model name Summary Required when external device is External connected. UTY-XWZXZ5 Connect Kit Use to connect with external devices and air conditioner PCB. External Input UTY-XCSXZ2 Optional External Connect Kit is and Output PCB necessary for installation. Communication Use to connect Non-polar 2-core wired UTY-TWRXZ2...
  • Page 57: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOUG09LZAH1 AOUG12LZAH1 AOUG15LZAH1...
  • Page 58: Specifications

    1. Specifications Type Inverter heat pump Model name AOUG09LZAH1 AOUG12LZAH1 AOUG15LZAH1 Power supply 208/230 V ~ 60 Hz Available voltage range 187—253 V Starting current Cooling 1,089 (1,850) 1,171 (1,990) 1,218 (2,070) Airflow rate CFM (m Heating 1,089 (1,850) 1,089 (1,850) 1,348 (2,290) Type ×...
  • Page 59: Dimensions

    11-7/16 (290) 1-5/16 (33) 1-3/16 (30) Side view Front view Side view Airflow Hole Hole Hole 15-11/16 (399) 7-1/16 (180) Drain port Ø1-5/8 (42) Side view (Valve part) Bottom view - 55 - 2-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 2. Dimensions...
  • Page 60: Installation Space

    Max. 7 (200) Max. 7 (200) 24 (600) or more 24 (600) or more 4 (100) or more 4 (100) or more 4 (100) or more 10 (250) or more - 56 - 3-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 3. Installation space...
  • Page 61 Obstacles at rear and above. Max. 11 (300) 60 (1,500) or more 10 (250) or more 60 (1,500) or more 10 (250) or more 8 (200) or more - 57 - 3-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 3. Installation space...
  • Page 62 Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed. - 58 - 3-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 3. Installation space...
  • Page 63: Refrigerant Circuit

    Cooling Heating : Thermistor (Compressor temperature) : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 59 - 4-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 4. Refrigerant circuit...
  • Page 64: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 - 60 - 5-1. Models: AOUG09LZAH1, AOUG12LZAH1, and AOUG15LZAH1 5. Wiring diagrams...
  • Page 65: Capacity Compensation Rate For Pipe Length And Height Difference

    Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOUG09LZAH1 and AOUG12LZAH1 NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length COOLING 0.877 0.874 0.956 0.891...
  • Page 66: Model: Aoug15Lzah1

    6-2. Model: AOUG15LZAH1 NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length COOLING 0.951 0.950 0.979 0.967 0.966 Indoor unit is higher than outdoor unit *1 0.988 0.983 0.971 0.970 0.994 0.992 0.987 0.975 0.974 1.002 1.000...
  • Page 67: Additional Charge Calculation

    7. Additional charge calculation 7-1. Models: AOUG09LZAH1 and AOUG12LZAH1 Refrigerant type R410A lb oz 2 lb 14 oz Refrigerant amount 1,300 ¢ Refrigerant charge 49 or less 66 (Max.) Total pipe length 0.22 oz/ft 15 or less 20 (Max.) (20 g/m) Additional charge 7-2.
  • Page 68: Airflow

    8. Airflow 8-1. Model: AOUG09LZAH1  Cooling Airflow 1,850 1,089  Heating Airflow 1,850 1,089 8-2. Model: AOUG12LZAH1  Cooling Airflow 1,990 1,171  Heating Airflow 1,850 1,089 - 64 - 8-1. Model: AOUG09LZAH1 8. Airflow...
  • Page 69: Model: Aoug15Lzah1

    8-3. Model: AOUG15LZAH1  Cooling Airflow 2,070 1,218  Heating Airflow 2,290 1,348 - 65 - 8-3. Model: AOUG15LZAH1 8. Airflow...
  • Page 70: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ Model: AOUG09LZAH1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000...
  • Page 71: Sound Level Check Point

    ¢ Model: AOUG15LZAH1  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz 9-2.
  • Page 72: Electrical Characteristics

    10. Electrical characteristics Model name AOUG09LZAH1 AOUG12LZAH1 AOUG15LZAH1 Voltage 208/230~ Power supply Frequency MCA *1 14.4 17.5 Starting current MAX. CKT. BKR *3 Power cable Wiring Size spec. *2 Connection Limited cable *4 wiring ft (m) 69 (21) length *1: Minimum Circuit Ampacity (Calculation based on UL60335-2-40) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 73: Safety Devices

    11. Safety devices Model Type of Protection form protection AOUG09LZAH1 AOUG12LZAH1 AOUG15LZAH1 250 V, 15 A 250 V, 20 A Circuit Current fuse (Main PCB) 250 V, 5 A protection 250 V, 3.15 A 257±18 °F (125±10 °C) Activate Fan motor stop...
  • Page 74: Accessories

    12. Accessories Part name Exterior Part name Exterior Installation manual Cable tie - 70 - 12. Accessories...

This manual is also suitable for:

Aoug12lzah1Aoug15lzah1Asug09lzasAsug12lzasAsug15lzas

Table of Contents