Instructions For Maintenance And Initial Check; General Warnings; Initial Check - Immergas Victrix Tera 28 1 Instructions And Warnings

Hide thumbs Also See for Victrix Tera 28 1:
Table of Contents

Advertisement

3
INSTRUCTIONS FOR
MAINTENANCE AND

INITIAL CHECK.

3.1

GENERAL WARNINGS.

ATTENTION:
operators who install and service the
appliance must wear the personal pro-
tective equipment (PPE) required by
applicable law.
Note: the list of possible PPE is not
complete as they are indicated by the
employer.
ATTENTION:
before performing any maintenance
operation, make sure:
- you have disconnected the power to
the appliance;
- you have closed the gas cock;
- you have discharged the pressure from
the system and domestic hot water
circuit.
Risk of material damage after using sprays and liq-
uids to search for leaks.
Leak sprays and liquids clog the reference hole P1 (Fig.
40) of the gas valve, damaging it irreparably.
During installation and maintenance, do not use spray
or liquids in the upper area of the gas valve (side referring to the
electric connections)
Supply of spare parts.
The device's warranty shall be rendered null and void
if unapproved or unsuitable parts are used for main-
tenance or repairs. These will also compromise the
product's compliance, and the said product may no
longer be valid and fail to meet the current regulations.
With regard to the above, only use Immergas original spare parts
when replacing parts.
If additional documentation needs to be consulted for
extraordinary maintenance, contact the Authorised
After-Sales Service.
40
3.2
INITIAL CHECK.
To commission the boiler:
- make sure that the type of gas used corresponds to
boiler settings;
- check connection to a 230V-50Hz power mains,
correct L-N polarity and the earthing connection;
- make sure the central heating system is filled with water and
that the pressure gauge indicates a pressure of 1-1.2 bar;
- switch the boiler on and ensure correct ignition;
- check the proper calibration of the number of fan revolutions;
- check the CO
flow rate in the flue:
2
- maximum
- intermediate
- minimum
- ensure that the safety device intervenes in the event of gas
supply failure and check the relative intervention time;
- check activation of the main switch located upstream of the
boiler;
- check that the intake and/or exhaust terminals are not
blocked;
- ensure activation of all adjustment devices;
- seal the gas flow rate regulation devices (if settings are mod-
ified);
- ensure production of domestic hot water;
- check tightness of water circuits;
- check ventilation and/or aeration of the installation room
where provided.
Even if just one single safety check provides a negative result,
do not commission the system