Daikin EWAD E-SS Series Installation, Operation And Maintenance Manual page 39

Air-cooled single circuit screw chiller
Table of Contents

Advertisement

Model
Disconnect Switch Size
Short circuit rating (note 1)
Recommended Fuses
Minimum Recommended Wire Size (note 2)
Maximum Wire Size (note 3)
Model
Disconnect Switch Size
Short circuit rating (note 1)
Recommended Fuses
Minimum Recommended Wire Size (note 2)
Maximum Wire Size (note 3)
Note 1:
Short-circuit current ratings are referred to a 0.25 s duration of short circuit.
Note 2:
Correct wire sizing must take into account the actual ambient temperature of the installation and the protection device insta lled on-site.
Recommended wire size is made according to standard EN60204-1 – Table 6.E with the following assumptions:
-
Recommended protection devices (fuses)
-
70°C PVC stranded copper conductors
-
40°C ambient temperature
Wire sizing is different as installation and operation conditions are different from the above mentioned values. The voltage drop from the
point of supply to the load must not exceed 5% of the nominal voltage under normal operating conditions. In order to co mply with this
requirement, it can be necessary to use conductors having a larger cross-sectional area than the minimum value reported on the above
table.
Note 3:
Maximum wire size is the maximum allowed by the disconnect switch terminals. In case a larger conductor size is needed, conta ct
factory for asking special incoming lugs.
Model
Disconnect Switch Size
Short circuit rating (note 1)
Recommended Fuses
Minimum Recommended Wire Size (note 2)
Maximum Wire Size (note 3)
Model
Disconnect Switch Size
Short circuit rating (note 1)
Recommended Fuses
Minimum Recommended Wire Size (note 2)
Maximum Wire Size (note 3)
Note 1:
Short-circuit current ratings are referred to a 0.25 s duration of short circuit.
Note 2:
Correct wire sizing must take into account the actual ambient temperature of the installation and the protection device installed on-site.
Recommended wire size is made according to standard EN60204-1 – Table 6.E with the following assumptions:
-
Recommended protection devices (fuses)
-
70°C PVC stranded copper conductors
-
40°C ambient temperature
Wire sizing is different as installation and operation conditions are different from the above mentioned values. The voltage drop from the
point of supply to the load must not exceed 5% of the nominal voltage under normal operating conditions. In order to co mply with this
requirement, it can be necessary to use conductors having a larger cross-sectional area than the minimum value reported on the above
table.
Note 3:
Maximum wire size is the maximum allowed by the disconnect switch terminals. In case a larger conductor size is needed, contact
factory for asking special incoming lugs.
D–EIMAC00708-16EN - 39/76
EWAD 100E ÷ 400E-SL
EWAD 100E-SL EWAD 120E-SL EWAD 130E-SL EWAD 160E-SS EWAD 180E-SL
400 A
400 A
25 kA
25 kA
125 A gG
160 A gG
70 mm2
95 mm2
2x185 mm2
2x185 mm2
EWAD 210E-SL EWAD 250E-SL EWAD 300E-SL EWAD 350E-SL EWAD 400E-SL
400 A
400 A
25 kA
25 kA
200 A gG
250 A gG
120 mm2
150 mm2
2x185 mm2
2x185 mm2
ERAD 120E ÷490E-SS
ERAD 120E-SS ERAD 140E-SS ERAD 170E-SS ERAD 200E-SS ERAD 220E-SS
400 A
400 A
25 kA
25 kA
125 A gG
160 A gG
70 mm2
95 mm2
2x185 mm2
2x185 mm2
ERAD 250E-SS ERAD 310E-SS ERAD 370E-SS ERAD 440E-SS ERAD 490E-SS
400 A
400 A
25 kA
25 kA
200 A gG
250 A gG
120 mm2
150 mm2
2x185 mm2
2x185 mm2
400 A
400 A
25 kA
25 kA
160 A gG
200 A gG
95 mm2
120 mm2
2x185 mm2
2x185 mm2
400 A
400 A
25 kA
25 kA
315 A gG
355 A gG
2x95 mm2
2x95 mm2
2x185 mm2
2x185 mm2
400 A
400 A
25 kA
25 kA
160 A gG
200 A gG
95 mm2
120 mm2
2x185 mm2
2x185 mm2
400 A
400 A
25 kA
25 kA
315 A gG
355 A gG
2x95 mm2
2x95 mm2
2x185 mm2
2x185 mm2
400 A
25 kA
200 A gG
120 mm2
2x185 mm2
400 A
25 kA
355 A gG
2x120 mm2
2x185 mm2
400 A
25 kA
200 A gG
120 mm2
2x185 mm2
400 A
25 kA
355 A gG
2x120 mm2
2x185 mm2