Thank you for purchasing this OMRON product. This INSTRUCTION
MANUAL describes the information such as function, performance, and
how to use the product required for using the product.
• Please operate the product by the qualified specialist having the
electrical know how.
• Read this instruction manual with enough, and use the product with
enough understanding.
• Keep this instruction manual close at hand and use it for reference
during operation.
H 5F
TI ME SW
IT CH
3 0 0
PM
O N
PW
5 0 0
PM
H 5F
TIM E SW
ITC H
3 0 0
PM
ON
PW
5 0 0
PM
1
2.4 VA ma x.
2
3
RE S.
4
OMRON Corporation
© All Rights Reserved.
INSTRUCTION MANUAL
H 5F
TIM E SW ITC
H
3 0 0
PM
ON
PW
5 0 0
PM
10 0 to 24 0V
AC
50 /60 Hz
1
15 A
2.4 VA ma x.
25 0V AC
2
10 A
24 VD C
3
RE S.
4
■  S afety   
Precautions
‥‥  ‥    P 1
■  T able of Contents
‥‥  ‥    P 5
■  O peration
‥‥  ‥    P 7
■  I nstallation
‥‥‥ P29
1617398-8D

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the H5F and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Omron H5F

  • Page 1 DIGITAL DAILY TIME SWITCH INSTRUCTION MANUAL English Thank you for purchasing this OMRON product. This INSTRUCTION MANUAL describes the information such as function, performance, and how to use the product required for using the product. • Please operate the product by the qualified specialist having the electrical know how.
  • Page 2: Safety Precoutions

    Safety Precautions ●  Key to Warning Symbols Indicates information that,if not followed,could CAUTION result in relatively serious or minor injury, property damage,or faulty operation. ●  Graphic symbol ●  W arning against electric shocks    Notification of possible electric shocks under   certain conditions.  ●  General warning    Notification of general, unspecified prohibition   items.  ●  P rohibition against disassembly    Notification of disassembly of products, when   doing so can cause possible electric shocks. ...
  • Page 3: Precautionary Information

    ● Precautionary Information CAUTION Do not touch any of the terminals while power is being supplied. Doing so may result in electric shock. Be sure to mount the terminal cover after wiring. Do not use the product where flammable or combustion gases are present. There may be a risk of explosion.
  • Page 4: Precautions For Safe Use

    Precautions for Safe Use Please comply strictly with the following instructions which are intended to ensure safe operation of the controller. (1) Application of voltages other than the rated voltage may seriously damage the internal elements. (2) Separate the Time Switch from any potential sources of noise, such as high-voltage lines.
  • Page 5 (8) None of the Time Switch components are user-replaceable, including the battery. Suitability for Use OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of the products in the customer's application or use of the product.
  • Page 6: Table Of Contents

    Table of Contents Safety precoutions ・・・・・・・・・・・・・・・・・・・・・・・・・ 1 Precautionary information ・・・・・・・・・・・・・・・・・・・ 2 Precautions for safe use ・・・・・・・・・・・・・・・・・・・・ 3 Suitability for use ・・・・・・・・・・・・・・・・・・・・・・・・・・・ 4 Table of contents ・・・・・・・・・・・・・・・・・・・・・・・・・ 5.6 Operation 1. Nomenclature・・・・・・・・・・・・・・・・・・・・・・・・・・ 2. Operating functions・・・・・・・・・・・・・・・・・・・・・ 3. Selecting the mode ・・・・・・・・・・・・・・・・・・・・・ 4. Setting the time・・・・・・・・・・・・・・・・・・・・・・・・ 5.
  • Page 7 23.24 13. Override and automatic return operation・・ 14. Program check function・・・・・・・・・・・・・・・・・・ 15. Operation while the power supply is OFF ・・  26  26  16. Setting precautions・・・・・・・・・・・・・・・・・・・・・ 17. Setting examples ・・・・・・・・・・・・・・・・・・・・・・ 18. Troubleshooting ・・・・・・・・・・・・・・・・・・・・・・・    Installation 23.24 1. Dimensions and mounting dimensions・・ 2.
  • Page 8: Operation

    Operation 1.Nomenclature <Front Panel> SELECT/HOLIDAY KEY MODE KEY • Used to set/clear specified days. • Used to switch between run mode, time • Used to enter/leave holiday setting adjustment mode, and the operation mode. SU MO TU WE TH FR SA TMR/ P KEY h KEY •...
  • Page 9: Operating Functions

    2. Operating Functions Operating function Explanation Remarks Output control is determined by the ON/OFF time Timer Operation P . 1 1   settings. (ON / OFF) • Minimum setting interval: 1 min • One ON/OFF set counts as two steps. •...
  • Page 10: Selecting The Mode

    3. Selecting the Mode All of the modes can be selected using , and Keys. MODE HOLIDAY TEST Move to the desired mode using the method shown below. • The days and times when • Set a special day when the output will actually turn ON/OFF Time Switch will not operate are displayed chronologically.
  • Page 11: Setting The Time

    4. Setting the Time 【Example】 Changing the current time setting from Wednesday 10:30 am to Monday 4:00 am. The color indicates flashing SU MO TU WE TH FR SA ①  Press the for 1 s min. to enter time MODE 10 30 adjustment mode.
  • Page 12: Setting Timer Operation

    5. Setting Timer Operation 【Example】 Setting the Time Switch to operate from Monday to Friday between 8:30 am and 5:15 pm Non-operation Operation Operation Operation Operation Operation Non-operation 8:30 am 5:15 pm The color indicates flashing SU MO TU WE TH FR SA ① ...
  • Page 13 The color indicates flashing SU MO TU WE TH FR SA ⑤  Press the WRITE Key. -- -- (Repeat steps 2 to 5 to make other settings if necessary.) P  SU MO TU WE TH FR SA ⑥  Press the Key to enter operation date MODE setting mode.
  • Page 14: Setting Pulse-Output Operation

    6. Setting pulse-output operation Using pulse-output operation, the Time Switch can be set to operate at the same time every day for a fixed period. 【Example】 Setting the Time Switch to turn ON for 30 s from 8:25 am, Monday to Friday. Non-operation Operation Operation Operation...
  • Page 15 The color indicates flashing SU MO TU WE TH FR SA ⑤ Set the ON time (the time when pulse-output 8 25 operation starts) to 8:25 am using the P  Keys. m/ P WD SU MO TU WE TH FR SA ⑥ Press the Key.
  • Page 16: Setting Partial Operation On Specified Day

    7. Setting partial operation on specified day The Time Switch can be set to operate according to only some of the settings on a user-specified day. 【 Example 】   Monday to Friday: ON at 8:30 am; OFF at 0:30 pm ON at 1:15 pm;...
  • Page 17 The color indicates flashing SU MO TU WE TH FR SA ⑤  Press the Key. WRITE 1 15 Set the time to 1:15 pm using the Keys. m / P WD P  SU MO TU WE TH FR SA ⑥  Press the Key.
  • Page 18: Changing (Confirming) Settings

    8. Changing (Confirming) Settings Changing (confirming) timer operation settings 【Example1】 Changing the ON time for program No.1 from 8:30 am to 7:45 am The color indicates flashing SU MO TU WE TH FR SA ①  Enter operation time setting mode using the 8 30 Key.
  • Page 19 Changing (confirming) pulse-output operation settings 【Example 2】 Changing the pulse width from 30 s to 20 s The color indicates flashing SU MO TU WE TH FR SA ①  Enter operation time setting mode using key. The pulse width is displayed. MODE P ...
  • Page 20: Clearing The Settings

    9. Clearing the Settings Clearing the settings for individual programs 【Example 1】 Clearing the settings for program No.2 The color indicates flashing SU MO TU WE TH FR SA ①  Enter operation time setting mode using 8 30 S  Key.The ON time for program No.1 MODE P ...
  • Page 21 Clearing all settings The color indicates flashing SU MO TU WE TH FR SA ①  Enter operation time setting mode or operation 8 30 S  date setting mode using the Key. MODE P  SU MO TU WE TH FR SA ② ...
  • Page 22: Setting (Temporary) Holidays

    10. Setting (Temporary) Holidays Stopping operation for a certain day in the current week and restoring normal operation from the following week 【Example】 Stopping operation for Friday and Saturday in the current week and resuming normal operation from the following week The color indicates flashing SU MO TU WE TH FR SA ① ...
  • Page 23: Summer Time(Dst)

    11. Summer Time (DST) Each time the Key is pressed, the present time will Time Switch between the (standard) present time and the present time + 1 hour (summer time). The color indicates flashing SU MO TU WE TH FR SA SU MO TU WE TH FR SA 3 30 4 30 ● ...
  • Page 24: Override And Automatic Return Operation

    13. Override and automatic return operation In Override and automatic return operation, the status can be set to ON or OFF directly using the Out ON/OFF switch. This status is then held until the next ON/OFF operation based on the regular settings. 【Example1】...
  • Page 25 【Using Override and automatic return operation for pulse-output operation 】 Pulse-output operation proceeds in the following way when used for pulse-output operation. • If Override and automatic return operation is turned ON, output is turned ON for the set pulse width. •...
  • Page 26: Program Check Function

    14. Program check function The days and times at which output turns ON or OFF over the course of one week can be displayed continuously in the actual order in which they will occur. The color indicates flashing SU MO TU WE TH FR SA ① ...
  • Page 27: Operation While The Power Supply Is Off

    15. Operation while the Power Supply is OFF ① Output turns OFF. The output indicator and The color indicates flashing SU MO TU WE TH FR SA power indicator turn OFF. ② The Current day Indicator and next operation 4 30 Indicator are updated.
  • Page 28: Setting Examples

    17. Setting examples 【Example1】 Use the settings given below to turn ON output from 8:30 am on Monday right through to 0:30 pm on Saturday. 1:00 pm 0:30 pm ▲  ▲  ▲  ▲  ▲  ●  ●  ●  ●  ●  8:30 am 2:00 pm Operation time settings: Operation date settings:...
  • Page 29: Troubleshooting

    18. Troubleshooting Probable cause and Reference Problem countermeasure page The Time Switch does Is the power actually ON? not operate when the Check that the power is ON using the power is turned ON. display. Is the Time Switch wired correctly? P.31 Check the wiring.
  • Page 30: Installation

    Installation 1. Dimensions and Mounting Dimensions ■ H5F-B (Flush-mounting Model ) [mm] ● Dimensions ● Mounting Dimensions Panel  Y92A-48 Dust Cover (sold separately)  63.7 Y92F-30  Flush-mounting   Adapter(accesory) R0.5max 84.8 Note:  88.7 Pay attention to the   orientation of the adapter   when mounting two or more   Terminal cover time switches in a vertical   (accesory) +0.5 or horizontal. ■ H5F-FB (Surface-mounting Model) [mm] ● Dimensions ● Mounting Dimensions Y92A-48E Dust Cover (sold separately) 42.1 (50) M4 tapping screws (2; provided) ...
  • Page 31 ■ H5F-KB (Surface/Track Mounting Models) [mm] ● Dimensions 43.1 50.5 Y92A-48E Dust Cover (accesory) ● Mounting Dimensions DIN Track mounting Mounting with a mounting bracket Mounting bracket ※63.1 M4 tapping screw hole (accesory) ※※71.8 (50.5) ※76.1 Mounting space ※※84.8 <Size of tapping screw hole>...
  • Page 32: Connections

    2. Connections ● H5F-B ● H5F-FB ● H5F-KB (Rear View) (Front View) (Front View) Power supply Output Output Power • Power supply and output are not Output Power supply connected internally. supply • Terminal screw size : M3.5 3. Wiring Read the following information before performing wiring.
  • Page 33 ● Separate Power Supplies for Time Switch and Load Using with an electromagnetic relay or contactor Direct control with If using the Switch beyond its ratings is unavoidable, use it together with an electromagnetic switch or contactor the Time Switch Single phase Three phase Power supply Power supply...
  • Page 34: Output (Built-In Relay) Life Expectancy

    10,000 operations min. for a lamp load of 300 W at 100 VAC The higher the ambient temperature is, the shorter the Time Switch's life expectancy will be. 5. Ratings and Performance Characteristics Supply voltage 24VDC (H5F-B-90) Minimum setting 1min interval 100 to 240VAC 50/60Hz(other)
  • Page 35: Iec Standards

    6. EN/IEC Standards Basic insulation is used between the power supply and outputs. Connect the output terminals only to devices without exposed charged parts and with the basic insulation appropriate for the maximum operating voltage. For 24VDC input type Connect the power supply terminals only to devices without exposed charged parts and with the basic insulation appropriate for the maximum operating voltage.
  • Page 36 2113 Australia Phone: 1-847-843-7900 Phone: 61-2-9878-6377 Fax: 1-847-843-7787 Fax: 61-2-9878-6981 CANADA SINGAPORE OMRON CANADA INC. OMRON ELECTRONICS PTE. LTD. 885 Milner Avenue, Scarborough, Ontario, 55 Ubi Avenue 1 M1B 5V8 CANADA #05-01, Singapore 408935 Phone: 1-416-286-6465 Phone: 65-6547-6789 Phone: 1-514-636-6676(French Language)