Trouble-Shooting List
Error
Code
Error Message
Display
Ground Fault
E0
GFCI Fault
Circuit Interrupter
fault
Bus High
Bus Voltage High
E6/E11
Fault/Bus
/Bus Fault
Fault
E9
No Utility
Utility loss
Ground
Leakage current
E10
Current
high
Fault
Over
E13
Temperatu
Inverter too hot
re Fault
PV Over
PV input voltage
E15
Fault
high
M Grid
Grid voltage out of
E17
Volt Fault
range
Isolation
Insulation
E18
Fault
Resistance high
Current
E19
DC bias high
DC Offset
Over
E12
Over current fault
Current
Relay 1/2
E24
Relay fault
Fault
MGrid
Grid frequency out
E29
FreqFault
of range
Maintenance&Trouble Shooting
Possible Fault
Ground Fault Circuit
Interrupter fault
· PV Input voltage high
· AC side poor connection
· utility loss
· AC side circuit breaker
turn off
· AC side poor connection
· inverter fault
1. poor earthing, leakage
current high
2. PV(+) or PV(-) earthed
· inverter enclosure too hot
· temperatrue sensor fault
· PV array's Voc high
· grid voltage out of the
setting range
· PV(+) or PV(-
) earthed
· AC side DC bias high
· grid fluctuate
· AC side poor connection
· inverter fault
· grid fluctuate
· grid frequency out of
setting range
20
Correctie Measure
restart the inverter
· check PV input voltage within
450Vdc(up to 3.0kw model),
500Vdc(up to 5.0kw model)
· check AC connector, circuit breaker
well connection
· grid back to the normal, the inverter
will restart automatically
· replace the AC circuit breaker
· check AC connector well
connection
· after seceral retart the fault remains,
replace inverter
1. check the AC output wring and
restart the inverter
2. check PV array wiring
· turn off the inverter still the
temperature down to the normal. Or
install the inverter at a well ventilated
site.
· replace the temperature sensor
· re-design the PV array
configuration
· measure the PV array voltage is the
same as inverter displayed.
· grid back to the normal, the inverter
will restart automatically
· check Country standard setting is
correct
check the resistance between PV(+)
and ground, PV(-) and ground bigger
than 2MΩ.
restart the inverter
· the inverter will restart automatically
· check the AC output wring and
restart the inverter
restart the inverter
· grid back to the normal, the inverter
will restart automatically
· check inverter frequency setting
range correct