Assignment planning
3.5 Configuring the mechanical structure
3.5.4
Arrangement of the modules for the function "Change During Operation" and / or
"Redundancy"
Arrangement rules
The following rules apply to the location of the modules in an ET 200M:
● An ET 200M can only be installed on one mounting rack (rail), because coupling to other
● A maximum of 8 signal modules, function modules or communication processors may be
● The IM 153-x and all the SM / FM / CP must be connected to active bus modules.
With the respective configuration, you can compatibly operate the combinations of interface
modules IM 153-2 specified in the following table on active bus modules BM IM/IM.
Table 3- 3
If the redundant IM 153-2 are
configured as ...
IM 153-2AA02
IM 153-2BA00
IM 153-2BA01
IM 153-2BA81
IM 153-2AB01
IM 153-2BB00
Note
The active bus modules 6ES7195-7HD10-0XA0 and 6ES7195-7HD80-0XA0 are given two
yellow markings for easier identification. These marks indicate that only IM 153-2Bx00 or
IM 153-2Bxx1 can be connected to these bus modules.
44
mounting racks via interface modules is not permissible.
inserted to the right alongside the IM 153-x.
Compatible versions of the IM 153-2 interface module
... and the interface modules are
connected to the active bus
module 6ES7195-...,
7HD00-0XA0
7HD10-0XA0
7HD10-0XA0
7HD10-0XA0
7HD80-0XA0
7HD80-0XA0
7HD00-0XA0
7HD10-0XA0
7HD10-0XA0
Operating Instructions, 12/2008, EWA-4NEB780600602-08
then the following IM 153-2 can
be operated compatibly:
IM 153-2AA02
IM 153-2BA00
IM 153-2BAx1
IM 153-2BA00
IM 153-2BAx1
IM 153-2BA00
IM 153-2BAx1
IM 153-2BAx1
IM 153-2BAx1
IM 153-2BA81
IM 153-2AB01
IM 153-2BB00
IM 153-2BB00
IM 153-2BB00