Functions
8.4 Redundancy with IM 153-2
8.4
Redundancy with IM 153-2
Use
You can operate the interface module IM 153-2 redundantly
● on the SIMATIC S7-400H (e.g. CPU 417-4H)
● with GSD file on any DP master (e.g. S5-115H)
● with software redundancy
● to standard
Conditions for the ET 200M
● Configuration with active bus modules
● 2 x IM 153-2 on bus module BM IM/IM
● Software redundancy and system redundancy (SR) are possible with the
● Flying redundancy (FR) is possible with IM 153-2 / -2 FO as of 6ES7153-2Bxx1-0XB0
● In redundant mode the function SYNC / FREEZE is not activated.
Note
If the function SYNC / FREEZE is nevertheless activated in a redundant system, the user
bears the responsibility for the behavior of the H system (e.g. when changing over).
● In a redundant system, you can only use the IM 153-2 interface module on DP masters
162
When configuring with a GSD file, the redundant operation of the IM 153-2 interface
module can take place only in DPV0 mode. This operating mode is set differently
dependent on the configuration tool.
For the basic package
is required. The optional software includes an online help in which the use and function of
the software redundancy is described.
Specification slave redundancy V1.2, Nov. 2004 of the PROFIBUS user organization;
order no: 2.212
– System Redundancy (SR)
– Flying Redundancy (FR)
The configuration with active bus modules 6ES7195-7HD10-0XA0 or
6ES7195-7HD80-0XA0 ensures a greater availability of the ET 200M.
The arrangement specifications named in the chapter "Installation (Page 59)" apply to the
active bus modules and interface modules used.
IM 153-2 / -2 FO as of 6ES7153-2AA02-0XB0 / -2AB01-0XB0
– The redundant master system must be configured in accordance with the demands on
H systems.
– The GSD file of the IM 153-2 (GSD rev. 5) must be imported to the configuration tool.
Note
STEP 7
offers no support for configuring an H system with flying redundancy.
that support the "fail safe" parameter. The IM 153-2 will not run on DP masters that do not
support this parameter, and the BF LED flashes.
Tip: You can see in the GSD-file of the DP master whether this "fail safe" is supported.
STEP 7
, the optional software
Operating Instructions, 12/2008, EWA-4NEB780600602-08
SIMATIC S7 Software Redundancy
ET 200M