KAITERRA
www.kaiterra.com
Kaiterra Sensedge Mini
Modbus User Manual
JULY 2020

Advertisement

loading

Summary of Contents for Kaiterra Sensedge Mini

  • Page 1 KAITERRA www.kaiterra.com Kaiterra Sensedge Mini Modbus User Manual JULY 2020...
  • Page 2 Ethernet network. Sensedge Mini provides Modbus/RTU support via the RS-485 port on the device. Sensedge Mini can still upload data to the cloud via Wi-Fi or Ethernet when Modbus is used for local communication. ...
  • Page 3: Prepare For Configuration

    Run the cables through the opening on the plate, and plug the 4-pin Phoenix pin plug into the corresponding terminals on the back of the device. The default Modbus address is set as 1, and can be changed later via the Kaiterra Configuration Tool.
  • Page 4: Connect To Network

    C. Connect to Network Open network settings on your computer and look for the Wi-Fi network that starts with “Kaiterra”. Connect your computer to that network. Click “Identify device” to identify the device currently being configured if multiple devices are present. The STATUS light will flash yellow rapidly for about 5 seconds.
  • Page 5 You can choose your AQI standard and customize your AQI calculation in the Kaiterra Configuration Tool. AQI stands for Air Quality Index, an index calculated based on the concentration of a set of air pollutants. Sensedge Mini offers AQI value in the Modbus communication so that you can integrate the information into your local system.
  • Page 6: Communication Protocol - Modbus Rtu

    KAITERRA www.kaiterra.com Communication Protocol - Modbus RTU Data type and format: Data length=8 Stop bit=1 Transmission rate=9600 Check: even Data format Address Function Data Error check Data length 16 digit CRC code  (Cyclic Redundancy Check) Default modbus address code is 0x01 Commands ...
  • Page 7: Register Address

    KAITERRA www.kaiterra.com Register Address Address Content R/W Property Comments Input register 0 PM2.5 0-999 ug/m3 Input register 1 TVOC 0-9999 ppb Input register 2 Temperature -30.0-50.0℃ Input register 3 Humidity 0.0%-100% RH Input register 4 0-9999 ppm Input register 5...
  • Page 8 KAITERRA www.kaiterra.com Holding Register 0 Modbus address Min 1, Max 247 code Holding Register 1 LED ON/OFF 1 - LED ON; 0 - LED OFF Holding Register 2 LED board ON/OFF 1 - LED board ON; 0 - LED board OFF * Other features could be customized upon requests.