Page 2
Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button functions can be found on page How to scroll through menus and make different settings is described on page Set the indoor climate INDOOR CLIMATE HOT WATER MY INSTALLATION...
1 Important information VVM 500 must be installed via an isolator Safety information switch. The cable area has to be dimensioned based on the fuse rating used. This manual describes installation and service proced- ures for implementation by specialists. Symbols The manual must be left with the customer.
Improper disposal of the product by the user results in administrative penalties in accordance with current le- Serial number gislation. Caution You need the product's ((14 digit) serial number for servicing and support. NIBE VVM 500 Chapter 1 | Important information...
Part no. 064 136 Part no. 064 137 F2120-16 3x400V F2120-20 3x400V Part no. 064 139 Part no. 064 141 Check the software version of compatible older NIBE air/water heat pumps, see page 18. NIBE VVM 500 Chapter 1 | Important information...
Transport Leave a free space of 800 mm in front of the product. All service on VVM 500 can be carried out from the front. VVM 500 should be transported and stored vertically in a dry place. However, the VVM 500 may be carefully 10-25 laid on its back when being moved into a building.
Current sensor Flow meter* Cable* Union nut* Copper pipe with flange to energy meter* *Only applies to Norway. LOCATION The kit of supplied items is placed on top of the product. NIBE VVM 500 Chapter 2 | Delivery and handling...
Remove the screws from the upper and lower edges. Twist the cover slightly outward. Move the hatch backwards and slightly to the side. Pull the cover to one side. Pull the hatch forwards. Chapter 2 | Delivery and handling NIBE VVM 500...
F2120-12 0.35 highest recommended temperatures are 55 °C on the (1x230V) supply line and 45 °C on the return line, but VVM 500 F2120-12 0.35 can handle up to 70 °C on the supply line. F2120-16 0.38...
Page 15
NOTE 1,000 Switch (SF1) must not be moved to "" or " " until VVM 500 has been filled with water. Otherwise the temperature limiter, thermostat NOTE and the immersion heater etc can be damaged. Expansion vessel is not supplied with the product.
Page 16
SYSTEM DIAGRAM SYMBOL KEY VVM 500 consists of a hot water coil, immersion heater, Symbol Meaning circulation pumps, buffer vessel, control system and is Shut-off valve prepared for use with solar panels. VVM 500 connects to the climate system. Non-return valve...
XL3 Connection, cold water G25 int XL4 Connection, hot water G25 ext. XL8 Connection, docking from heat pump G25 int XL9 Connection, docking to heat pump G25 int XL30 Connection, expansion vessel G25 int NIBE VVM 500 Chapter 4 | Pipe connections...
VVM 500 can be installed in several different ways, A climate system is a system that regulates indoor some of which are shown below. comfort with the help of the control system in VVM 500 Further option information is available at nibe.eu...
Page 19
CONNECTING HOT WATER CIRCULATION Product Software version A circulation pump can be controlled by VVM 500 to F2120 all versions circulate the hot water. The circulating water must have F2300 a temperature that prevents bacterial growth and NIBE SPLIT HBS 05: all versions scalding, and national standards must be satisfied.
• If the building is equipped with an earth-fault breaker, VVM320 Electrical installation and service must be car- VVM 500 should be equipped with a separate one. ried out under the supervision of a qualified electrician. Cut the current with the circuit •...
Page 21
Removing the cover, input circuit board Insert the screwdriver (A) and pry the catch carefully downwards (B). Angle out the cover and remove it. Push the catch down. Angle out the cover and remove it. NIBE VVM 500 Chapter 5 | Electrical connections...
Page 22
CABLE LOCK Use a suitable tool to release/lock cables in the indoor module terminal blocks. Chapter 5 | Electrical connections NIBE VVM 500...
(AA1). All installations must be carried out in accordance VOLTAGE FOR THE CONTROL SYSTEM with current norms and directives. The connection cable can be found on the reverse of VVM 500. (See dimen- NOTE sions diagram below.) Only applies to power connection of 3x400V.
Page 24
CONNECTING SENSOR Room sensor VVM 500 is supplied with a room sensor enclosed (BT50). The room sensor has a number of functions: Shows current room temperature in the display on VVM 500. Option of changing the room temperature in °C.
Page 25
COMMUNICATION If VVM 500 is to be connected to the heat pump, it is connected to terminal blocks X4:13, X4:14 and X4:15 on the input board (AA3). AA3-X4 VVM 500 and F2040 / NIBE SPLIT HBS 05 Inomhusmodul VVM 500 AA3-X4...
3x400V (maximum electrical output, connected to 7 kW) Electrical ad- Max L1 (A) Max L2 (A) Max L3 (A) dition (kW) The image shows the dip-switch (AA1-SF1) in the factory setting, that is 6 kW. Chapter 5 | Electrical connections NIBE VVM 500...
Page 27
Emergency mode thermostat The supply temperature in emergency mode is set using a thermostat (FQ10-BT30). It can be set to 35 (preset, För markvärme! e.g. underfloor heating) or 45 °C (e.g. radiators). För frånluftsvärme! NIBE VVM 500 Chapter 5 | Electrical connections...
Go into menu 5.4 "soft in/outputs" on the display to se- unit. The multi-core cable between the enclosure and lect to which AUX connection each function connects. VVM 500 must have a cable area of at least 0.5 mm². soft in/outputs 5.4 block heating...
Page 29
The example above uses the inputs AUX1 (X6:9-10) and AUX2 (X6:11- An external switch function can be connected to 12) on the input board (AA3). VVM 500 to activate various functions. The function is Selectable output activated during the time the switch is closed.
Page 30
• away mode for "smart home" (complement to the functions in menu 4.1.7) This accessory may require a software up- date in your VVM 500. The version can be Control checked in the “Service info” menu 3.1. • circulation pump for hot water circulation Visit nibeuplink.com...
Page 31
(BT64) for cooling out and the cooling set point value. If the “active cooling 4-pipes” accessory has been activ- ated, the function is switched off. Cooling is then oper- ated from the accessory instead. NIBE VVM 500 Chapter 5 | Electrical connections...
Use cable type LiYY, EKKX or similar. Refer to the accessory manual for further instructions. Indoor module AA3-X4 AA3-X4 Accessory card 1 AA5-X4 AA5-X4 -X10 Accessory card 2 AA5-X4 AA5-X4 -X10 Chapter 5 | Electrical connections NIBE VVM 500...
Page 33
RMU 40 to the indoor module’s terminal block X4:9-12 on the input board AA3. Use cable type LiYY, EKKX or equivalent. Refer to the accessory manual for further instructions. AA3-X4 AA3-X4 Indoor module Accessories AA9-X1 12V A B GND NIBE VVM 500 Chapter 5 | Electrical connections...
Turn off the power supply to VVM 500. Check that the switch (SF1) is in position " ". Vent VVM 500 through the vent valves (QM20) and other climate systems through their relevant vent Check that the drain valve is fully closed and that valves.
VVM 500 will start automatically. Make settings for the system here. The start guide will appear at each restart of VVM 500, until it is deselected on the last page. NIBE VVM 500 Chapter 6 | Commissioning and adjusting...
Page 36
Vent the installation through the vent Connect the pipe for docking in from the heat pump valves (QM20). When venting, VVM 500 must be off. (XL8) with the pipe out to the heat pump (XL9). Enter menu 5.2.2 System settings and deactivate the heat pump.
°C increment. COOLING IN 2-PIPE SYSTEM VVM 500 contains a built-in function for operating cooling in a 2-pipe system down to 17 °C, factory setting 18 °C. outdoor temp. °C This requires that the outdoor module can perform cooling.
1 °C. temperature and there is no hot water or heating require- affect pool temperature (accessory is required) ment, VVM 500 starts pool heating. Here you set whether pool temperature should be af- Untick "activated" to switch off the pool heating.
Page 39
With overcapacity mode on "SG Ready", the desired pool temperature (start and stop temperature) is increased by 2 °C. NOTE The function must be connected to two AUX inputs and activated in menu 5.4. NIBE VVM 500 Chapter 6 | Commissioning and adjusting...
• confirm selections of sub menus/options/set values/page in the start guide. BACK BUTTON The back button is used to: • go back to the previous menu. • change a setting that has not been confirmed. Chapter 7 | Control - Introduction NIBE VVM 500...
HOT WATER Hot water temp. compressor in the outdoor module or addi- tional heat is blocked in VVM 500. These can, for example, be blocked depend- ing on which operating mode is selected in menu 4.2, if blocking is scheduled in menu Information about 4.9.5 or if an alarm has occurred that blocks...
Page 42
Back button. Mark the applicable option. One of the options is pre-selected (white). Press the OK button to confirm the selected option. The selected option has a green tick. Chapter 7 | Control - Introduction NIBE VVM 500...
Page 43
(at the page number) has been marked. Press the OK button to skip between the steps in the start guide. If the start guide is left on this page it closes automatically in 60 min NIBE VVM 500 Chapter 7 | Control - Introduction...
Menu 3 - INFO 3 - INFO 3.1 - service info 3.2 - compressor info 3.3 - add. heat info 3.4 - alarm log 3.5 - indoor temp. log * Accessories are needed. NIBE VVM 500 Chapter 8 | Control – Menus...
5.11.1.1 - heat pump 5.11.1.2 - charge pump (GP12) 5.12 - country * Accessory needed. Go to the main menu and hold the Back button in for 7 seconds to access the Service menu. NIBE VVM 500 Chapter 8 | Control – Menus...
Page 48
Factory setting stop temp. lux: 55 °C there is an alarm in the display here. Here you set the start and stop temperature of the hot water for the different comfort options in menu 2.2. Chapter 8 | Control – Menus NIBE VVM 500...
Page 49
Factory setting: 16 A Caution Here you set the max. electrical output of the internal electrical addition in VVM 500 and the fuse size for the An incorrectly set ventilation flow can damage installation. the house and may also increase energy con- sumption.
Page 50
Setting range: on/off Factory setting: off Caution start diff additional heat This menu is only displayed if VVM 500 is Setting range: 0 – 2000 DM connected to a heat pump with inverter con- trolled compressor. Default values: 400 DM...
Page 52
Here, you can set the temper- ature in the solar panel at which the circulation pump is to start to prevent freezing. Chapter 8 | Control – Menus NIBE VVM 500...
Page 53
See the Installer Manual for HTS 40 for function descrip- tion. MENU 5.3.18 - POOL Here you select which pump to use in the system. NIBE VVM 500 Chapter 8 | Control – Menus...
Page 54
MENU 5.3.19 - ACTIVE COOLING 4 PIPE Caution Here you select which pump to use in the system. The software in VVM 500 must be software version 9085 or later. Visit nibeuplink.com MENU 5.3.21 - FLOW SENSOR / ENERGY click on the "Software" tab to download the METER latest software to your installation.
Page 55
The charge pump runs according to the current calculated flow temperatures. If less than seven periods operating mode for VVM 500. are to be used, set the remaining period times to 0 days. intermittent: The charge pump starts and stops 20...
Page 56
This allows access to country-specific settings in your product. Language settings can be made regardless of this selec- tion. Caution This option locks after 24 hours, after restarting the display and during program updating. Chapter 8 | Control – Menus NIBE VVM 500...
351.0 3.256 Servicing should only be carried out by persons 251.6 3.240 with the necessary expertise. 182.5 3.218 When replacing components on VVM 500 only 133.8 3.189 replacement parts from NIBE may be used. 99.22 3.150 74.32 3.105 EMERGENCY MODE 56.20...
Page 58
OK button you will return to the previous choose another file page (menu 7.1) where you can choose to start the up- date. This allows you to update the software in VVM 500. Chapter 9 | Service NIBE VVM 500...
Page 59
Via "save settings" you save the menu settings to the Here you can choose how current measurement values USB memory in order to restore them later or to copy from VVM 500 should be saved onto a log file on the the settings to another VVM 500. USB memory.
10 Disturbances in comfort In most cases, VVM 500 notes a malfunction (a malfunc- aid mode “aid mode” is a type of emergency mode. tion can lead to disruption in comfort) and indicates this This means that the indoor module produces heat and/or with alarms, and instructions for action, in the display.
Page 61
– If mode "manual" is selected, select "addition". tion is reduced, which can give smaller amounts of – Hot water is produced with VVM 500 in "manual" hot water. mode. If there is no air/water heat pump, "addition"...
The air/water heat pump’s compressor does not start • There is no heating or cooling demand (accessory is required for cooling). – VVM 500 does not call on heating, cooling or hot water. • Compressor blocked due to the temperature condi- tions.
DUC (computer sub-centre) in the An accessory card is also required if for example an extern- building. Communication is then performed using MOD- al circulation pump is connected to VVM 500 at the same BUS-RTU. time that the buzzer alarm is activated.
Page 64
The room unit is an accessory that allows the control and houses with two or more different heating systems that monitoring of VVM 500 to be carried out in a different part require different supply temperatures. of your home to where it is located.
Page 67
Part no. 069 400 *Applies in the case of normal comfort mode, tap flow 8 litres/minute and incoming cold water 10 °C. Increased hot water comfort can be obtained at lower tap flow. NIBE VVM 500 Chapter 12 | Technical data...
Tel: +46 (0)433-27 3000 kuzmin@evan.ru info@nibe.se nibe-evan.ru nibe.se SWITZERLAND NIBE Wärmetechnik c/o ait Schweiz Industriepark, CH-6246 Altishofen Tel. +41 (0)58 252 21 00 info@nibe.ch nibe.ch For countries not mentioned in this list, contact NIBE Sweden or check nibe.eu for more information.
Page 80
WS release date: 2020-06-17 07:45 Publish date: 2020-07-02 11:20 This manual is a publication from NIBE Energy Systems. All product illustrations, facts and data are based on the available information at the time of the publication’s approval. NIBE Energy Systems makes reservations for any factual or printing errors in this manual.