Setting Up And Tuning Pid Loops; Proportional Band (Pb) Settings; Integral Settings; Table 7.1 - Proportional Band Settings - Watlow CLS200 User Manual

Table of Contents

Advertisement

CLS200 Series User's Guide
Chapter 7: Turning and Control

Setting Up and Tuning PID Loops

After installing your control system, tune each control loop and then set the loop to automatic
control. When tuning a loop, choose PID parameters that will best control the process. This section
gives PID values for a variety of heating and cooling applications.

Proportional Band (PB) Settings

Table 7.1 shows proportional band settings for various temperatures in degrees Fahrenheit or
Celsius.
Table 7.1
As a general rule, set the proportional band to 10% of the setpoint below 1000° and 5% of the
setpoint above 1000°. This setting is useful as a starting value.

Integral Settings

The controller's integral parameter (TI) is set in seconds per repeat. Some other products use an
integral term called reset, in units of repeats per minute. Table 7.2 shows integral settings versus
reset settings.
NOTE! Tuning is a slow process. After adjusting a loop, allow about 20 minutes for the
change to take effect.
Proportional Band Settings
TEMPERATURE
PB
SETPOINT
-100 to 99
20
100 to 199
20
200 to 299
30
300 to 399
35
400 to 499
40
500 to 599
45
600 to 699
50
700 to 799
55
800 to 899
60
900 to 999
65
1000 to 1099
70
TEMPERATURE
PB
SETPOINT
1100 to 1199
75
1200 to 1299
80
1300 to 1399
85
1400 to 1499
90
1500 to 1599
95
1600 to 1699
100
1700 to 1799
105
1800 to 1899
110
1900 to 1999
120
2000 to 2099
125
2100 to 2199
130
TEMPERATURE
PB
SETPOINT
2200 to 2299
135
2300 to 2399
140
2400 to 2499
145
2500 to 2599
150
2600 to 2699
155
2700 to 2799
160
2800 to 2899
165
2900 to 2999
170
3000 to 3099
175
3100 to 3199
180
3200 to 3299
185
136