General Mounting Instructions - Berner Architectural High Performance 10 Installation & Maintenance Instructions Manual

Table of Contents

Advertisement

II. MOUNTING INSTRUCTIONS (General)
INDOOR MOUNTING ONLY -
The Architectural High Performance 10 Air Curtain is designed
to be an effective barrier against cold drafts in the winter
and hot air in the summer, flying insects and airborne
contaminants.
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, flush to the wall and
as close to the top of the door opening as possible. To ensure
peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sufficient load-carrying capacity to support
the weight of the air curtain(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the air curtain.
See Table 1.
IMPORTANT: A minimum of 1" is required above the top of the
air curtain for the installation and removal of the inlet
screen.
A.
When determining the mounting location for the air
curtain(s), make sure that nothing interferes with the
curtain of air developed when the discharge vanes are
directed from 0° to 20° toward the door opening. If the
air stream strikes any obstruction (the top edge of the
doorway, a door opening device, etc.), the effectiveness
of the air curtain will be greatly reduced. See Figure 2.
B.
For optimum performance, the bottom of the air curtain
(discharge nozzle) should be no more than 1" above the
top of the door opening with the air curtain(s) mounted
flush to the wall. If the air curtain must be mounted
higher, it must be spaced out from the wall 3/8" for
every inch the air curtain is above the door opening. See
Figure 3. For optimum protection, any void between the
air curtain and the wall should be sealed along the full
length of the air curtain.
C.
Do not block (obstruct) the air intake grill. Insufficient
airflow can cause the unit to overheat.
D.
Electric heated air curtain(s) shall:
1.
Have a minimum clearance of at least 4" from
the sides and 8" from the top for electric heated
units.
2.
Have a minimum clearance of at least 6' between
the bottom of the air curtain and the floor.
3.
Be installed Indoors Only.
E.
Proceed to either Section III - WALL MOUNTING or
Section IV - SUSPENDED MOUNTING
4" minimum
side
clearance
from
combustible
material*
EXTERIOR
*Electrically Heated Units Only
WEIGHT IN POUNDS
Model
Unheated Electric Steam/Hot Water
AHD10-1036
65
AHD10-1042
68
AHD10-1048
70
AHD10-2048
95
AHD10-2060
125
AHD10-2072
130
AHD10-2084
140
AHD10-2096
145
AHD10-3096
165
AHD10-3108
170
AHD10-3120
175
TABLE 1 - Weight Chart
FLUSH WALL
MOUNT
Mounting
Screws
Mounting
Plate
Mounting
Screws
1"
Lower Lip
-4-
8" minimum*
AIR
Discharge
Nozzle
20˚
6' minimum
INTERIOR
Figure 2
71
74
76
107
137
142
152
157
183
188
193
EXTENDED
WALL MOUNT
Spacer
Seal
Spacer
2"
3/8"
Figure 3
98
104
109
135
171
182
198
209
229
241
249

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ahd10

Table of Contents