Uncrating; Mounting Instructions - Berner IDC12 Series Installation & Maintenance Instructions Manual

Table of Contents

Advertisement

I. UNCRATING
Carefully examine the carton(s) for damage before opening. If
the carton is damaged, immediately notify shipping company.
If the unit(s) were shipped on wooden skids, remove protective
wood and banding straps securing the carton(s) to the skid.
Open the carton(s) and remove all protective packaging. Im-
mediately verify that the electrical rating nameplate located on
the cover matches the electrical power supply available. Retain
the shipping carton(s) until the unit(s) is installed and properly
operating.
ACCESSORIES: If the unit(s) were ordered with optional electri-
cal accessories (door switch, control panel, etc.), the accessories
may be found in the carton containing the unit or in a separate
carton(s) accompanying the unit(s). Check all of the cartons/
skids for accessories before discarding.
II. MOUNTING INSTRUCTIONS
(General Notes for All Mounting Configurations)
INDOOR MOUNTING - Environmental/Insect/Dust Control
OUTDOOR MOUNTING (Unheated Only) - Insect/Dust Control
A. Berner IDC12/IDC14 air doors are designed to be mounted
by their end flanges without the need for intermediate
support. Each end flange contains (8) total ½" holes located
on all (4) sides to facilitate mounting flexibility and the easy
addition of mounting accessories. Units may be attached to
the wall directly, suspended from overhead, or supported
by brackets. The style of door will determine the best
Model
Electric
Ambient
Heat
IDC12-1036
90
IDC12-1042
101
IDC12-1048
109
IDC12-1060
119
IDC12-2060
160
IDC12-2072
167
IDC12-2078
178
IDC12-2084
188
IDC12-2096
203
IDC12-3096
233
IDC12-2108
212
IDC12-3108
251
IDC12-2120
221
IDC12-3120
272
IDC12-3132
289
IDC12-3144
304
IDC12-4144
335
IDC12-4156
355
IDC12-4168
376
IDC12-4180
391
IDC12-5180
419
IDC12-4192
405
IDC12-5192
435
* Weight includes heater and duct transition
TABLE 1
Weight by Unit Type
Hot
Steam
Water
Heat
Heat
96
130
130
107
145
145
115
158
158
125
178
178
172
219
219
179
229
229
190
244
244
200
258
258
215
282
282
251
312
312
224
296
296
269
335
335
233
311
311
290
362
362
307
390
390
322
412
412
359
443
443
379
471
471
400
499
499
415
523
523
449
551
551
429
544
544
465
574
574
mounting method and; as a general rule, use the mounting
configuration that positions the air door as close to the top
of the doorway as possible without interfering with door
operation.
B. The IDC12/IDC14 Series air door is designed to be an
effective barrier against cold drafts in the winter and hot
air in the summer. To achieve optimum protection, the
unit should be mounted on the inside of the building, flush
to the wall and as close to the top of the door opening as
possible. To ensure peak performance keep the air stream
free of obstructions. If the air door cannot be installed flush
with the wall, be sure to seal the gap between the wall and
the back of the air door along the entire length of the unit to
prevent airflow through this void.
C. The air door will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
D. Before mounting the air door, check the supporting
structure to verify that it has sufficient load-carrying capacity
to support the weight of the unit(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the unit. See
Tables 1 & 2.
Model
Indirect
Gas
Heat*
IDC14-1036
125
IDC14-1042
125
IDC14-1048
125
IDC14-1060
125
IDC14-2060
130
IDC14-2072
130
IDC14-2078
130
IDC14-2084
130
IDC14-2096
130
IDC14-3096
145
IDC14-2108
130
IDC14-3108
145
IDC14-2120
130
IDC14-3120
145
IDC14-3132
145
IDC14-3144
145
IDC14-4144
225
IDC14-4156
2 @ 130
IDC14-4168
2 @ 130
IDC14-4180
2 @ 130
IDC14-5180
2 @ 145
IDC14-4192
2 @ 130
IDC14-5192
2 @ 145
* Weight includes heater and duct transition
TABLE 2
-2-
Weight by Unit Type
Electric
Steam
Ambient
Heat
Heat
93
99
133
104
110
148
112
118
161
122
128
181
163
175
222
170
182
232
181
193
247
191
203
261
206
218
285
236
254
315
215
227
299
254
272
338
224
236
314
275
293
365
292
310
393
307
325
415
338
362
446
358
382
504
379
403
534
394
418
561
422
452
589
408
432
584
438
468
614
Indirect
Hot Water
Gas
Heat
Heat*
133
125
148
125
161
125
181
125
222
145
232
145
247
145
261
145
285
145
315
270
299
145
338
270
314
145
365
270
393
285
415
285
446
285
504
2 @ 145
534
2 @ 145
561
2 @ 145
589
2 @ 225
584
2 @ 145
614
2 @ 225

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Idc14 seriesIdc12-1036Idc12-1042Idc12-1048Idc12-1060Idc12-2060 ... Show all

Table of Contents