Notes: Single phase motor has three lines, first use the multimeter check the three
lines resistor, the biggest value two lines parallel the start capacitor (recommend
the capacitor volume is 150UF/250V), the other line(common-coil) connect the
power terminal. Then use the multimeter check the common coil with the other two
lines resistor, the lower one connects another power terminal.

6. Basic Operation

Motor debugging
(1)AM Pump
Default parameter one key start and stop
Same power level, determine the direction of operation (F0.16)
Adjust motor parameters and corresponding protection parameters
according to the application
(2)PMSM Pump
Set motor parameter (F5.00-F5.06, Motor series 、 Frequency、 Speed、
Voltage、Current、Power)
Rotating self-tuningF5.12(SI22 SI30), F5.20 (SI23)
Judge the direction of the pump
(3)Single Phase Pump
 Connect the starting capacitor between the main coil and the auxiliary
coil
 Shield output phase loss
 Running judge the direction of the pump