3�2 REFRIGERANT TYPE AND INSTALLED

LOCATION

This heat pumps CPT6, CPT8, CPT12 and CPT15
contain R32, which is an environmentally friendly
refrigerant with a GWP (Global Warming Potential) of
675. R32 has the safety in use classification of A2L,
being low toxicity and lower flammability. In practical
terms it is very difficult to ignite an A2L refrigerant,
but this classification requires a risk assessment to
be undertaken for the possibility of refrigerant being
released by accident into an area connected to the
heat pump, considering the application, location of
components, and the installed refrigerant charge. This
installation guidance can form the framework for such a
risk assessment for the installation.
Model
Refrigerant
R32 kg
charge
Minimum area
Notes
*Assumed worst case for access category: a - general access and location class: I - mechanical equipment
in occupied space; both as defined in line with EN378-1 2016 section 5.1 table 4 and section 5.3.
*Min Area is calculated in line with section C.2 on EN378-1 2016 (calculation C.2)
INTERPRETATION
Please refer to the installation situations below for how
to apply the minimum area stated above.
Pool outside and heat pump outside:
Automatically meets the minimum area requirement
because outside space is unlimited.
Pool outside and heat pump inside a plant room:
Automatically meets the minimum area requirement
because the room must open to the outside for heat
pump airflow and the outside space is unlimited.
1006905 ISSUE 2
All flammable refrigerants will not ignite if the
concentration level in a room stays below their lower
flammability limit (LFL). European standard EN378
defines requirements to remain far below the lower
flammable limit in case of accidental leakage. By
choosing the location as dictated by EN378-1:2016
the probability of forming a flammable atmosphere
can be eliminated. Please refer to the minimum
area for each product and the interpretation below
regarding locations of heat pump and swimming pool.
This information is provided as a guide only and does
not supersede the regulations or health and safety
requirements
CPT6ALY
CPT8ALY
0.9
1.0
6.9
8.5
Pool inside and heat pump outside:
The pool hall must exceed the minimum area
requirement shown above.
Pool inside and heat pump inside a plant room,
isolated from the pool hall:
The pool hall must exceed the minimum area
requirement shown above.
Pool inside and heat pump inside a plant room,
ventilated to the pool hall:
The pool hall and plant room combined must exceed
the minimum area requirement shown above.
CPT12ALY
CPT15ALY
1.5
1.5
19.1
19.1
13