Troubleshooting Guide - Vermont Castings DVRT36 Homeowner's Installation & Operating Manual

Vermont indoor gas fireplace operating manual
Table of Contents

Advertisement

Troubleshooting – Honeywell VS8421
START
Gas Supply On
YES
Pilot Lights With Piezo
Ignitor
YES
Pilot Stays Lit
YES
Pilot Lights Main Burner
YES
SYSTEM OK
10002428
Vermont Castings, Majestic Products DVRT36/ 39/ 43
Remove the Window Frame Assembly before service work.
NO
NO
NO
NO
CHECK
Supply Line Hooked Up
Shutoff Valve Open
Lockout Has Engaged. Wait 60
Seconds And Try Again.
For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.
All Wiring Connections
Replace Piezo Ignitor
For Air In The Lines
Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
All Wiring Connections
Replace Thermopile
Thermocouple Needs A Min. Of
14mv
Defective Valve. Turn To Pilot,
Meter Should Read Greater
Than 100mv. If Not, Replace.
Valve Is Turned On
Wall Switch Is Not Turned On.
Watch For Grounded Wires!
Thermopile Needs A Min. 325mv.
Plugged Burner Orifice
35