Vermont Castings 33XDV Installation Instructions And Homeowner's Manual page 18

Direct vent models
Hide thumbs Also See for 33XDV:
Table of Contents

Advertisement

XDV Direct Vent Gas Fireplace
Vertical Sidewall Installation
Twist Lock Pipe
STEP 1
Locate vent opening on the wall. It may be necessary
to first position the fireplace and measure to obtain hole
location. Depending on whether the wall is combustible
or noncombustible, cut opening to size. (Fig. 33) (For
combustible walls first frame in opening.)
NOTE: When using flex vent, the opening will have to
be measured according to the 1/2" (13 mm) rise in 12"
(305 mm) vent run.
Combustible Walls (Fig. 33): Cut a 9³⁄₈"H x 9³⁄₈" W
(240 x 240 mm) hole through the exterior wall and
frame.
Noncombustible Walls (Fig. 33): Hole opening must
be 7.5" (190 mm) in diameter.
Vent Opening for Combustible Wall
9³⁄₈"
(240 mm)
9³⁄₈"
(240 mm)
Fireplace Hearth
Opening for Noncombustible Wall
7¹⁄₂"
(190 mm)
Fig. 33 Locate vent opening on wall.
STEP 2
Measure wall thickness and cut adjustable zero clearance
sleeve parts to proper length (MAXIMUM 12"/305 mm).
Assemble sleeve and attach to firestop with #8 sheet metal
screws (supplied). Install firestop assembly. (Fig. 34)
VO584-100
Vent Opening
Zero clearance sleeve is only required for
2/99 djt
combustible walls.
STEP 3
Place fireplace into position. Measure the vertical height
(X) required from the base of the flue collars to the
center of the wall opening. (Fig. 35)
18
Framing
Detail
VO584-100
Adjustable
Zero Clearance
Sleeve
#8 Screws
(2)
Firestop
Adjustable Zero Clearance Sleeve
ZCS101
Fig. 34 Adjustable zero clearance sleeve.
Zero Clearance Sleeve
3/11/99 djt
X
Fig. 35 Vertical height requirements.
STEP 4
Apply a band of silicone to the inner and outer flue
collars of the fireplace and using appropriate length of
pipe section(s) attach to fireplace with three (3) screws.
Follow with the installation of the inner and outer elbow,
again secure joints with three (3) sheet metal screws.
Wipe off any excess silicone.
STEP 5
Measure the horizontal length requirement including a
2" (51 mm) overlap, i.e. from the elbow to the outside
wall finish plus 2", or the distance required if installing a
second 90° elbow. (Fig. 26)
Always install horizontal venting on a level
plane.
STEP 6
Use appropriate length of pipe section - telescopic or
fixed - and install. The sections which go through the
wall are packaged with the starter kit, and can be cut to
suit if necessary.
Sealing vent pipe and firestop gaps with high tem-
perature sealant will restrict cold air being drawn in
around fireplace.
Max. Length
12" (305mm)
#8 Screws (2)
#8
Screws
(2)
ZCS101
X
FP1181
10009383