Step 5 - Elevate Unit; Step 6 - In Long-Line Applications, Install Liquid-Line Solenoid Valve; (Lsv); Step 7 - Make Piping Connections - Bryant Evolution Extreme 186CNV Installation Instructions Manual

Variable speed air conditioner with puron refrigerant
Hide thumbs Also See for Evolution Extreme 186CNV:
Table of Contents

Advertisement

186CNV: Installation Instructions
Step 5 – Elevate Unit
Elevate unit per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate drainage
of unit.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Do not allow water and/or ice to build up in base pan.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Locate the unit in such a way that it is stable in all circumstances
including adverse weather conditions.
Step 6 – In Long-Line Applications, Install Liquid-Line
Solenoid Valve (LSV)
For refrigerant piping arrangements with equivalent lengths of
than 80 ft. (24.38 m) and/or when elevation difference between indoor
and outdoor unit is greater than ±20 ft. (±6.10 m), follow the piping
configuration and liquid line solenoid valve (LSV) accessory
requirements from the Residential Piping and Long-line guideline. CCH,
start gear and piston changes do not apply. If required by Long-Line
Guideline, install LSV kit, part no. KHALS0401LLS. LSV should be
installed within 2 ft. (0.61 m) of outdoor unit with flow arrow pointing
toward outdoor unit.
Make the necessary electrical connections as shown in
and by following the Installation Instructions included with accessory
kit.
IMPORTANT: Flow arrow must point toward outdoor unit.
Furnace or
User Interface
Fan Coil
Green
A
Yellow
B
White
C
Red
D
S1
Optional Remote
Room Sensor
S2
Fig. 3 – Liquid Line Solenoid Electrical Connection
(Required for long line applications)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig. 3
and
Variable Speed
AC or HP
A
A
B
B
Connection (optional)
C
C
D
D
LLS
C
LS
Wall Control
D
C
B
A
Humidifier
Fig. 4 – Evolution Furnace or Fan Coil Wiring with Communicating
Step 7 – Make Piping Connections
greater
PERSONAL INJURY AND UNIT DAMAGE
HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or
final unit disposal. Use all service ports and open all flow-control
devices, including solenoid valves.
Fig. 4
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Do not leave system open to atmosphere any longer than minimum
required for installation. PVE oil in compressor is extremely
susceptible to moisture absorption. Always keep ends of tubing sealed
during installation.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
A180243
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical
rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm)
may be buried without further special consideration. Do not bury lines
longer than 36 in. (914.4 mm).
Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct size
and condition. For tubing requirements beyond 80 ft. (24.38 m),
substantial capacity and performance losses can occur. Follow the pipe
sizing recommendations in the 186CNV Product data to manage these
losses.
4
Furnace or Fan Coil
D
C
B
A
D not required
'C' connection optional
Variable Speed AC
WARNING
!
CAUTION
!
CAUTION
!
HP or AC
C
B
A
A200204

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents