Final Checks; Care And Maintenance - Bryant Evolution Extreme 186CNV Installation Instructions Manual

Variable speed air conditioner with puron refrigerant
Hide thumbs Also See for Evolution Extreme 186CNV:
Table of Contents

Advertisement

186CNV: Installation Instructions
Table 8 – Malfunction Lockout Durations
Code
Title
24-58 5V PCM External Power Out of Range
25-61 Invalid Model Plug Malfunction
25-62 Model Plug Missing Malfunction
25-63 VFD Model Mismatch
28-71 Fuse 1 Open Malfunction
28-72 Fuse 2 Open Malfunction
Compressor High Pressure Limit
31-58
Malfunction
32-55 Compressor Low Pressure Limit Lockout
32-59 Low Pressure Disable
33-55 Compressor Low Discharge Limit Lockout
Compressor High Temperature Limit
34-58
Malfunction
Compressor High Compression Limit
35-58
Malfunction
Compressor Low Compression Limit
36-55
Lockout
38-53 Compressor Starting Malfunction
38-54 Compressor No Pump
38-71 VFD Estimator Malfunction
39-53 Fan Start Malfunction
39-55 Unexpected Fan Shutdown Malfunction
39-58 Fan Motor Malfunction
53-41 OST Open / Low Temp
53-42 OST Shorted / High Temp
57-41 P1 Open Malfunction
57-42 P1 Shorted Malfunction
57-43 P1 Sensor Malfunction
58-41 P2 Open Malfunction
58-42 P2 Shorted Malfunction
58-43 P2 Sensor Malfunction
61-41 Reversing Valve Solenoid Open
* unlikely to clear on its own; see Service Manual for troubleshooting steps

FINAL CHECKS

IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal
edges to prevent rub-through or wire pinching.
2. Ensure that all wiring and tubing is secure in unit before adding
panels and covers. Securely fasten all panels and covers.
3. Tighten service valve stem caps to 1/12-turn past finger tight.
4. Leave Users Manual with owner. Explain system operation and
periodic maintenance requirements outlined in manual.
5. Fill out Dealer Installation Checklist and place in customer file.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Code
Time
64-41 EXV-H Phase Open
Duration of Event
64-44 EXV-H Power Short to Ground
Duration of Event
64-45 EXV-H Phase Short to Ground
Duration of Event
65-41 EXV-VI Phase Open
Permanent*
65-44 EXV-VI Power Short to Ground
Permanent*
65-45 EXV-VI Phase Short to Ground
Permanent*
66-41 VFD Control Relay Coil Open
2 hours
66-42 VFD Control Relay Coil Shorted
81-53 PFC Malfunction
2 hours
81-54 Unbalanced PFCM Malfunction
Permanent*
81-58 VFD System Wiring Error
2 hours
82-53 VFD Reset with Power Dropout Malfunction
2 hours
82-55
2 hours
82-56 Low Voltage Shutdown Malfunction
82-57 Line Over Voltage Malfunction
2 hours
83-55 Compressor Current Limit 3 Lockout
4 hours
83-56 Compressor Current Limit 4 Lockout
30 minutes
83-57 Compressor Underspeed Shutdown
4 hours
84-58 VFD Overtemp Malfunction
1 hour
85-53 DC Under Voltage Malfunction
4 hours
85-54 DC Over Voltage Malfunction
30 minutes
86-46 VFD Communication Malfunction
Duration of Event
87-53 VFD Initialization Malfunction
Duration of Event
88-55 Unexpected VFD Reset Malfunction
Duration of Event
88-71 VFD Internal Malfunction - Current Sensor
Duration of Event
88-73 VFD Internal Malfunction - DC Link Sensor
Permanent*
88-74 VFD Internal Malfunction - PFCM Sensor A
Duration of Event
88-75 VFD Internal Malfunction - PFCM Sensor B
Duration of Event
88-76 VFD Internal Malfunction - Line Volt Sensor
Permanent*
88-78 VFD Internal Malfunction - DC Discharge
Duration of Event

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equipment
failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas,
such as coastal applications. See Owner's Manual for information.
21
Table 8 – Malfunction Lockout Durations (Continued)
Title
VFD Shutdown with Power Dropout
Malfunction
Time
Duration of Event
Duration of Event
Duration of Event
Duration of Event
Duration of Event
Duration of Event
Duration of Event
Duration of Event
1 hour
4 hours
4 hours
1 hour
2 hours
1 hour
1 hour
2 hours
2 hours
1 hour
2 hours
1 hour
1 hour
1 hour
4 hours
1 hour
4 hours
4 hours
4 hours
4 hours
4 hours
4 hours