INSTALLATION
7
ELECTRICAL CONNECTIONS TO THE CONTROL PANEL
CAUTION: The connection must be carried out by a
qualified professional.
As the electrical wiring has been carefully checked in the
factory, the internal connections of the control panel must
not be modified under any circumstances.
The electrical connections of the boiler must conform with
the IEE wiring regulations in force and with the specifications
shown on the electrical drawings provided with the
equipment, and the instructions given below.
The equipment should be supplied by a circuit using an
omnipolar circuit breaker with an opening gap greater than
3mm.
DELUXE - control panel
All the connections are made to the 2 terminal blocks
provided for this purpose in the control panel.
The connection cables are routed towards the front via the 2
cut outs in the panel behind the boiler, and run in the wiring
duct towards the panel via the two rectangular cut outs of
the front top panel. The senor cables run on one side, the
cables carrying the 230 V supply on the other and are
supported on both sides by plastic clips.
Caution: The sensor wiring must be kept separate from
the other circuits. Inside the boiler, use the cable runs.
Outside the boiler, 2 wiring ducts at least 10cm apart
should be used.
12
For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytub.co.uk
8229-EN-44
Wiring is secured in the control panel using cable clips (6
cable clips are supplied in a separate packet); these are to
be fitted into the control panel base - see diagram below.
Caution: The maximum current which may be switched
by the outlet is 2 A, cos ϕ = 0.7 (= 450 W at he motor of
0.5 Méch., hp signal current less than 16 A), if the charge
exceeds one of these values, the control must be relayed
by means of a contractor. The outlet group is protected
by a 5 A fuse.