Control Panels; Burners - IDEAL evojet Installation And User Manual

150 - 1450kw
Table of Contents

Advertisement

All EVOJET boilers have been specified for use with a standard IDEAL TECH PRIME control.
The IDEAL TECH PRIME control panel is supplied with the boiler (UIN 212647) this is a single thermostatic control ena-
bling single stage operation and for all modulating applications. The instructions for this control are provided in a separate
manual supplied in the control panel box.
To enable two stage control a Two-Stage burner control kit (UIN 212644) should be requested.
Further control options for modulating burners via a Boiler Management System (BMS) or by an independent modulating
controller may be specified when the burner type is selected.
Oil & Dual Fuel - return water temperature control kit (UIN 215475)
In oil or dual fuel applicatoins the boiler should be prevented from condensing. To achieve this a 'return water temperature
control kit' must be fitted. This kit comprises a return water thermostat that operates a 'Shunt Pump' if the return water tem-
perature is less than 55 deg C.
The EVOJET boilers are designed to operate with Natural Gas, LPG or Oil using pressure-jet or premixed burners.
The burner specification will enable the choice of Two Stage / Fully Modulating & Low NOx operation.
The following burner & control options must be selected at the time of purchase.
Two Stage Burner
To operate a two stage burner the two stage burner control kit should be requested from the tech PRIME manual.
Modulating Burner
To operate a modulating burner the RWF50 modulating controller is required with a control thermistor. This option is selected
when specifying the burner type.
BMS (Boiler Management System) 0-10V
RIELLO Burners:
For operation from a 0-10v BMS signal the RIELLO signal converter should be specified when selecting the burner.
NUWAY Burners:
The burner model which includes the 0-10v converter must be specified.
Oil & Dual Fuel
The optional controls for Oil firing burners are either RWF50 Modulating or 0-10v BMS.
Commissioning
All installations must be commissioned by Ideal to activate warranty provision.

CONTROL PANELS

BURNERS

GENERAL
7

Advertisement

Table of Contents
loading

Table of Contents