Filling The Installation - IDEAL Viceroy GT Series Installation, Assembly And Servicing

Oil or dual gas fired boilers
Table of Contents

Advertisement

INSTALLATION
Example of installation of a Viceroy GT boiler with production
of domestic hot water through independent calorifier(s)
8219-EN-12
1.
Water flow flange
2.
Water return flange
3.
4 bars safety valve + manometer*
4.
Flow control device
5.
Air separator
6.
Air vent
7.
Valve
8.
Recycling pump
9.
Expansion tank
10. Drain valve
11. Desludging valve
12. Mixing valve
13. Check valve
14. Circulating pump
15. Pressure gauge

FILLING THE INSTALLATION

The boiler may be filled by the drain tap. Filling should be
done at a slow flow rate in order to purge all the air
contained in the boiler by the upper point of the installation.
Filling is always done with circulating pumps stopped.
General
Recommendations relating to the water system are contained
in BS.5449 Pt.1, BS5401 Pt.2. and BS.6880.
8
For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytub.co.uk
16. Sludge decantation pot
(particularly recommendation for older installations)
17. Independent calorifier
18. Safety unit, set and sealed at 7 bars with over flow
19. Pressure reducer (if system pressure >5.5bars)
20. Domestic cold water inlet
21. Domestic hot water flow
22. Calorifier heating pump
23. Domestic water circulating pump (optional)
24. DHW circuit return
25. Water meter (eventually)
26. Water treatment when TH > 25°
27. Heating system filler
(with circuit breaker in accordance with regulations).
* 6 bars maxi
MOST IMPORTANT: start up after partial or
total drain of the installation:
If all air does not purge naturally via an opened expansion
system, then in addition to automatic airvents able to ensure
continuous automatic elimination of air from the system while
it is running, the installation must also include manual
airvents so that all upper points of the installation can be
vented and so that when the installation is full of water it can
be verified that all air is eliminated before the boiler are fired.
Heating
Circuit
Viceroy GT Range
- Installation