Assembly/Hydraulic Connection - IDEAL Viceroy GT Series Installation, Assembly And Servicing

Oil or dual gas fired boilers
Table of Contents

Advertisement

Ventilation General
Detailed recommendations for air supply are quoted in BS.
6644. The ventilation requirements in this gas fired boiler
standard are also valid for oil fired boilers of the same heat
input.
3
ASSEMBLY
For the assembly of the boiler, refer to the removable leaflet
in the middle of the instruction book.
4
HYDRAULIC CONNECTION
Dimensional information required
Threaded drain 2"
Installation Recommendations
The installation of the boiler MUST be in accordance with the
following British Standards and Codes of Practice:
BS. 799 Pts. 4,5,6 & 7 Oil Burning Equipment
BS. 5410 Pts. 2 & 3
Installations for Space Heating and
Hot water Systems
BS. 5449 Pt.1
Hot Water Systems
BS. 5854
Flues and Flue Structures in Buildings
BS. 5885 Pt.1
Gas Burners - with outputs of
60kW upwards
BS.6644
Installation of Gas Fired Boilers
BS.6880
Low Temperature Hot Water Heating
Systems
BS.6891
Low Pressure Gas Pipework
British Gas
Industrial Gas Fired Boilers and
Publication No. IM.11 Air Heaters
Viceroy GT Range
- Installation
For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytub.co.uk
Remark: We draw your attention to the risks of corrosion of
boilers which are installed in or near rooms in which the
atmosphere can be polluted by chloride or fluoride
substances.
E.g. : industrial buildings (solvents), refrigerating machines,
etc...
In these cases, we cannot provide a warranty.
Water flow/return tapping
GT 8 to 10: Ø 2"1/2
GT 11 to 14: Ø 3"
8229-EN-06
Viceroy
GT 8 to 10
D mm
235
E mm
1427
The following must be confirmed with:
Current Building Regulations and Clean Air Act
Water Authority Regulations
Local Authority Regulations and Regional bylaws
Gas Safety Regulations
Any Special regional requirements of local Electricity and Gas
undertaking.
Fire Service and Insurance Company requirements.
All electrical wiring MUST comply with the current I.E.E.
regulations for the electrical equipment of buildings. In the
interests of safety, a competent installer should be employed
to effect the installation of the appliance. Manufacturer's
notes must NOT, in any way, be taken as over riding
statutory obligations.
INSTALLATION
Viceroy
GT 11 to 14
254
1447
7