Communication Specification; Communication Data; Table 22 - Communication Specifications; Table 23 - Read Command - York EX Series Installation, Operation & Maintenance Instructions Manual

Double effect direct fired absorption chiller-heater
Table of Contents

Advertisement

SECTION 4 - TECHNICAL DATA

Communication Specification

TABLE 22 - COMMUNICATION SPECIFICATIONS

Communication Protocol
Communication Path Type
IP Address
Subnet Mask
Function Code

Communication Data

TABLE 23 - READ COMMAND

ITEM
1
Set Point (Chilled/Hot water outlet
temp.)
2
Automatic stop temp. at cooling
mode (thermo-off temp)
3
Temp. difference of Automatic start/
stop control at cooling mode
4
Automatic stop temp. at heating
mode (thermo-off temp)
5
Temp. difference of Automatic start/
stop control at heating mode
6
Operation condition
7
Local/Remote mode condition
8
Solution pump condition
9
Refrigerant pump condition
10
Burner fan condition
11
Load limit condition
12
Control manipulated variable.
13
Failure signal.
14
Alarm signal
70
Modbus TCP
10BASE-T/100BASE-TX
(No. 1) 192.168.1.1, (No.2) 192.168.1.2, (No. 3) 192.168.1.3
255.255.255.0
Read Command
(Digital Signal) 0.1/Read Coil
(Analog Signal) 0.3/Read Holding Register
Write Command
(Digital Signal) 0.5/Force Single Coil
DISPLAY
UNIT
ADDRESS
7.0
°C
00001
5.0
°C
00003
5.0
°C
00005
62.0
°C
00007
5.0
°C
00009
0 or 1
-
00021
or 2
0 or 1
-
01001
0 or 1
-
01003
0 or 1
-
01005
0 or 1
-
01007
0 or 1
-
01009
100
%
00023
0 or 1
-
01011
0 or 1
-
01013
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
CONTENT
0050~1000 unit, 1 unit=0.1°C
0040~1000 unit, 1 unit=0.1°C
0001~1000 unit, 1 unit=0.1°C
0040~1000 unit, 1 unit=0.1°C
0001~1000 unit, 1 unit=0.1°C
0:STOP, 1:COOLING OPERATION,
2:HEATING OPERATION
0:LOCAL, 1:REMOTE
0:STOP,1:OPERATION
0:STOP,1:OPERATION
0:STOP,1:OPERATION
0:NORMAL OPERATION
1:LOAD LIMIT OPERATION
-0100~1100 unit, 1 unit=0.1%
0:NORMAL OPERATION
1:FAILURE OCCUR
0:NORMAL OPERATION
1:ALARM OCCUR
JOHNSON CONTROLS