York EX Series Installation, Operation & Maintenance Instructions Manual page 86

Double effect direct fired absorption chiller-heater
Table of Contents

Advertisement

SECTION 5 - COMMISSIONING
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (1/3)
User:
Model:
Insulation Resistance
Standard: 5 MΩ or more (with 500 V meg-
ger)
Circuit breaker
Solution circulation pump
Solution spray pump
Refrigerant pump
Purge pump
Thermal Relay Setting
Solution circulation pump
Solution spray pump
Refrigerant pump
Purge pump
Pump Discharge Pressure
Solution circulation pump
Solution spray pump
Refrigerant pump
NOTES:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
JOHNSON CONTROLS
86
MFG.No.:
R-Gnd
U-Gnd
Refrigerant Purity
A
Standard: 1.040 (kg/L) or less
A
Specific gravity
A
Turbidity
A
Purge Amount
MPa.G Standard: 4 cc/min or less
MPa.G Purge tank
MPa.G Absorber
User's machine code:
Electric Power Supply
S-Gnd
T-Gnd
Specification: AC
Standard: Within +/- 10% of spec.
R-S
V-Gnd
W-Gnd
R-T
S-T
R-Gnd
S-Gnd
T-Gnd
Temperature Setting
Set base temp.
Auto. stop temp
Auto restart diff.
Set base temp.
Auto. stop temp.
cc Auto. restart diff.
cc
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
V /
Hz
V
V
V
V
V
V
Cooling
°C
°C
°C
Heating
°C
°C
°C
5
JOHNSON CONTROLS

Advertisement

Table of Contents
loading