Section 4 - Technical Data; Table 4 - Typical Operational Range - York EX Series Installation, Operation & Maintenance Instructions Manual

Double effect direct fired absorption chiller-heater
Table of Contents

Advertisement

FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
This section includes technical information about
the unit, such as weight, dimensions, electrical data,
wiring, and sound data.

TABLE 4 - TYPICAL OPERATIONAL RANGE

PARAMETER
Chilled Water In
Chilled Water Out
Cooling Water In
Cooling Water Out
120 - 300 RT: 2 - 250 kPa(g)
Natural Gas Inlet
Pressure
360 - 1600 RT: 10 - 250 kPa(g)
JOHNSON CONTROLS

SECTION 4 - TECHNICAL DATA

ALLOWABLE RANGES
7 - 25°C
4 - 16°C
20 - 37°C
25 - 42°C
The numbers shown in Table 4 on page 31 are the
allowable ranges for each parameter. Not all combi-
nations are possible. Please check with your Johnson
Controls Service Center to see if your temperature dif-
ferential is possible.