DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (2/3)
OUTPUT VALUE
FUEL DAMPER POSITION
AIR DAMPER POSITION
FUEL PRIMARY PRESSURE
(P1)
FUEL SEcONDARY PRES-
SURE (P2)
FUEL cONSUMPTION (SEE
NOTES)
FUEL cONSUMPTION (SEE
NOTES)
ExhAUST GAS O
cON-
2
cENTRATION
ExhAUST GAS cO cON-
cENTRATION
ExhAUST GAS cO
cON-
2
cENTRATION
wIND BOx PRESSURE
DRAFT PRESSURE (P3)
FURNAcE PRESSURE (P4)
FLAME cURRENT
BURNER FAN OPERATION
cURRENT
ExhAUST GAS TEMPERA-
TURE
NOTES:
If gas flow rate is taken as m
/h, calculate m
3
P1
Gas
6
JOHNSON CONTROLS
cOMBUSTION DATA
MEASURED BY
%
Control panel
%
Damper pointer
%
Damper pointer
Pressure gauge
Pressure gauge
m
/h
Flow meter
3
m
N/h
Calculation or flow
3
meter
%
Exhaust gas analyzer
ppm
Exhaust gas analyzer
%
Exhaust gas analyzer
Water manometer
Water manometer
Water manometer
μA
Flame current meter
A
Cramp meter
°C
Control panel
N/h with fuel pressure and ambient temperature.
3
Air
P2
SPEcIFI-
STAN-
LOw
cATION
DARD
4.0~8.0
≤100
0~-49 kPa
≥2.0
≤250
Ambient temperature:
P4
P3
LD20247
SECTION 5 - COMMISSIONING
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
MIDDLE
hIGh
°C
JOHNSON CONTROLS
87
5