Smart DC Controller
HySecurity gate operators provide a 2-wire, serial interface (RS-485 connection) which allows remote access to
one or more operators.
When the physical connection is made and protocols are established, an SA (System Address) must be assigned
for each operator through its Installer Menu.
For network communication, choosing a "SA" of 1 to 4 establishes individual network polling addresses. HyNet
only utilizes numbers 1, 2, 3, or 4.
A "SA" of zero means no network communication is desired.
COM
COM
COM
COM
COMMON
COM
TERMINALS
COM
COM
COM
STOP
OPEN
CLOSE
OPEN
P ARTIAL
SENSOR 2
SENSOR 3
EXIT
LOOP
BLOCK
EXIT
IN OBS
LOOP
OUT OBS
LOOP
CENTER
LOOP
SENSOR 1
SENSOR
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
www.SecureOpeners.com | (800) 878-7829 | Sales@SecureOpeners.com
S A 0 ( O F F )
D R E S S
S Y S T E M A D
Refer to Table 1: HyNet LED Indicators on page 2.
4
Solid green means serial communication is active and
functioning well.
For IP network setup, refer to the HyNet Quick Start
5
manual supplied in the HyNet box.
To access Installer Menu, press
1
Menu button twice. Then, press
Reset and Open.
Press Select to navigate to
Installer Menu item "SA"
System Address.
SA 1
SYSTEM ADDRESS
OPEN
CLOSE
STOP
PREV
NEXT
SELECT
Press Select again to set gate
2
operator's system address
(Each gate operator attached
to the same HyNet must have
a unique SA number. Choose
1, 2, 3, or 4.)
To exit Menu mode, press Menu. The
3
gate operator returns to Run mode.
MENU
RESET