Operation; Operating Concept Of The Product; Start-Up; Prioritising Diverter Valve, Setting The Heating Circuit/Cylinder Charging - Vaillant VWL Series Operating Instructions Manual

Hydraulic station
Table of Contents

Advertisement

7

Operation

7.1

Operating concept of the product

The operating concept and the display and setting options of
the end user level are described in the operating instructions.
8

Start-up

8.1
Prioritising diverter valve, setting the
heating circuit/cylinder charging
90°
3
1.
If you want to manually set the prioritising diverter
valve, press the knob (1) and turn it 90° clockwise.
You can now turn the selection lever (2) to the re-
quired position.
Note
The notch (3) that points to the selection
lever's extension displays the position of the
selection lever. You can turn the selection
lever by 90° each time to select heating, cyl-
inder charging and the mid-position between
heating/cylinder charging (black). In automat-
ic mode, the selection lever can move to oth-
er intermediate positions (grey).
2.
If you want to actuate the heating circuit, turn the selec-
tion lever (2) to "Heating circuit".
3.
If you want to actuate the domestic hot water cylinder,
turn the selection lever to "Domestic hot water cylinder".
4.
If you want to actuate the heating circuit and the do-
mestic hot water cylinder, turn the selection lever to
"Heating circuit/domestic hot water cylinder".
0020291544_01 Hydraulic Station Installation and maintenance instructions
1
2
8.2
Checking and treating the heating
water/filling and supplementary water
Caution.
Risk of material damage due to poor-qual-
ity heating water
Ensure that the heating water is of suffi-
cient quality.
Before filling or topping up the installation, check the
quality of the heating water.
Checking the quality of the heating water
Remove a little water from the heating circuit.
Check the appearance of the heating water.
If you ascertain that it contains sedimentary materials,
you must desludge the installation.
Use a magnetic rod to check whether it contains mag-
netite (iron oxide).
If you ascertain that it contains magnetite, clean the in-
stallation and apply suitable corrosion-inhibition meas-
ures, or fit a magnetic filter.
Check the pH value of the removed water at 25 °C.
If the value is below 8.2 or above 10.0, clean the installa-
tion and treat the heating water.
Ensure that oxygen cannot get into the heating water.
Checking the filling and supplementary water
Before filling the installation, measure the hardness of the
filling and supplementary water.
Treating the filling and supplementary water
Observe all applicable national regulations and technical
rules when treating the filling and supplementary water.
Provided the national regulations and technical rules do not
stipulate more stringent requirements, the following applies:
You must treat the heating water in the following cases
If the entire filling and supplementary water quantity dur-
ing the operating life of the system exceeds three times
the nominal volume of the heating installation, or
If the guideline values listed in the following table are not
met, or
If the pH value of the heating water is less than 8.2 or
more than 10.0.
Total
Water hardness at specific system volume
heating
output
≤ 20 l/kW
ppm
mol/
kW
CaCO₃
< 50
< 300
< 3
> 50
200
2
to ≤ 200
> 200
150
1.5
to ≤ 600
> 600
2
0.02
1) Nominal capacity in litres/heating output; in the case of multi-
boiler systems, the smallest single heating output is to be used.
Operation 7
> 20 l/kW
> 50 l/kW
≤ 50 l/kW
ppm
mol/
ppm
mol/
CaCO₃
CaCO₃
200
2
2
0.02
150
1.5
2
0.02
2
0.02
2
0.02
2
0.02
2
0.02
1)
33