6 Electrical installation
6.12

Opening the control PCB's electronics box

B
1.
Hinge the electronics box forwards.
2.
Undo the four clips on the left and the right and the top
from the brackets.
6.13

Connecting the circulation pump

1.
Route the 230 V connection cable for the circulation
pump from the right and into the control PCB's electron-
ics box.
2.
Connect the 230 V connection cable to the plug from
slot X11 on the control PCB and plug it into the slot.
3.
Connect the connection cable for the external button
using terminals 1 (0) and 6 (FB) on the X41 edge con-
nector, which is supplied with the control.
4.
Plug the edge connector into slot X41 on the control
PCB.
5.
Set the circulation pump in the system control.
6.14
Connecting a limit thermostat for the
underfloor heating
Condition: Intermediate heat exchanger installed
Remove the S20 plug for the bypass line at terminal
X100 on the indoor unit's control PCB.
Connect the limit thermostat to plug S20 for the indoor
unit.
Condition: No intermediate heat exchanger installed
Connect the limit thermostat to plug S20 for the out-
door unit, → aroTHERM plus operating and installation
instructions.
32
A
C
6.15

Connecting the outdoor temperature sensor

Condition: No system control connected
Connect an outdoor temperature sensor to plug AF on
terminal X41 on the control PCB.
6.16
Connecting the domestic hot water
cylinder's temperature sensor
Condition: No system control connected
Connect a temperature sensor to the fed cable on the
X22 terminal block (connection terminals 19/20) on the
control PCB. The range of accessories includes a tem-
perature sensor (VR 10) with corresponding mating con-
nector and an extension with corresponding plug and
bush.
6.17
Connecting the external prioritising diverter
valve (optional)
Connect the external prioritising diverter valve to X14 on
the control PCB.
The connection to a permanently live phase "L" with
230 V and to a switched phase "S" is available.
Phase "S" is actuated by an internal relay and
releases 230 V.
6.18

Connecting the VR 70/VR 71 mixer module

1.
Connect the power supply for the VR 70/VR 71 mixer
module to X314 on the power supply PCB.
2.
Connect the VR 70/VR 71 mixer module to the eBUS
interface on the control PCB.
6.19

Connecting cascades

If you want to use cascades (max. seven units), you must
connect the eBUS line to contact X30 via the VR32b bus
coupler (accessory).
6.20
Closing the electronics box for the power
supply PCB
1.
Tighten all of the screws on the strain relief clamps.
2.
Close the cover on the electronics box.
3.
Hinge the electronics box back up.
6.21

Checking the electrical installation

After the installation is complete, check the electrical in-
stallation to ensure that the connections that have been
established are secured properly and are sufficiently in-
sulated.